CORRIGO E LON INTERFACE VARIABLE LIST MANU
LON-interface variable list Chapter 3 Corrigo heating 13
3.2 Table of Network Variables, Inputs (NVI)
Name SNVT type Description
nviOutdoorTemp SNVT_temp_p Outdoor temperature. Overrides signal from local sensor
nviHS1RoomTemp
SNVT_temp_p
Room temp HS1. Overrides signal from local sensor
nviHS2RoomTemp SNVT_temp_p Room temp HS2. Overrides signal from local sensor
nviHS3RoomTemp SNVT_temp_p Room temp HS3. Overrides signal from local sensor
nviHW1Setp
SNVT_temp_p
Setpoint, Supply HW1
nviHW2Setp SNVT_temp_p Setpoint, Supply HW2
nviDPSetp
SNVT_press_f
Setpoint Differential pressure
nviSndHrtB SNVT_time_sec Heart Beat (0 = disable)
nviTempHyst SNVT_temp_p Hysteresis for the variable type _temp_p (2)
nviPresHyst
SNVT_press_f
Hysteresis for the variable type _press_f (2)
nviSpeedHyst SNVT_speed Hysteresis for the variable type _speed (2)
nviVoltHyst
SNVT_volt_f
Hysteresis for the variable type _volt_f (Ao) (2)
Description explanation
(2) The hysteresis variables have nothing to do with the control software in the
controller. They are internal to the LON interface and are used for minimising
the amount of communication in the LON network.
(4) Only Corrigo version 2.1 or later. CorrigoEHeating2_1.APB and
CorrigoEHeating2_1.xif are also required.