CORRIGO E LON INTERFACE VARIABLE LIST MANU
LON-interface variable list Chapter 3 Corrigo heating 11
Name SNVT type Description
nvoRunInd SNVT_state Bit0 – HS1-P1A Run indication
Bit1 – HS1-P1B Run indication
Bit2 – HS2-P1A Run indication
Bit3 – HS2-P1B Run indication
Bit4 – HS3-P1A Run indication
Bit5 – HS3-P1B Run indication
Bit6 – HW1-P1 Run indication
Bit7 – HWB-P1 Run indication
Bit8 – Frequency converter Run indication
Bits9…15 not used
nvoDoValue SNVT_state Bit0 – Output signal Do1
Bit1 – Output signal Do2
Bit2 – Output signal Do3
Bit3 – Output signal Do4
Bit4 – Output signal Do5
Bit5 – Output signal Do6
Bit6 – Output signal Do7
Bits7…15 not used
nvoAlarm
SNVT_state_64
Bit0 – Run error P1A-HS1
Bit1 – Run error P1B-HS1
Bit2 – Run error P1A-HS2
Bit3 – Run error P1B-HS2
Bit4 – Run error P1A-HS3
Bit5 – Run error P1B-HS3
Bit6 – Run error P1-Hot water 1
Bit7 – Run error P1-Storage tank
Bit8 – Run error frequency converter
Bit9 – Expansion vessel alarm
Bit10 – External alarm
Bit11 – Alarm, Boiler
Bit12 – HS1 control error
Bit13 – HS2 control error
Bit14 – HS3 control error
Bit15 – HW1 control error
Bit16 – HW2 control error
Bit17 – Sensor error
Bit17 – Sensor error outdoor temperature (4)
Bit18 – High supply temp. HW1
Bit19 – High supply temp. Boiler
Bit21 – Low supply temp. Boiler
Bit22 – Pulse error, volume pulse
Bit23 – Pulse error, energy pulse
Bit24 – High 24 hour usage Cold water
Bit25 – High energy consumption
Bit24 – High hour usage Cold water
Bit27 – Leakage
Bit28 – Run error P1A&B-HS1