CORRIGO E LON INTERFACE VARIABLE LIST MANU

LON-interface variable list Chapter 3 Corrigo heating 11
Name SNVT type Description
nvoRunInd SNVT_state Bit0 HS1-P1A Run indication
Bit1 HS1-P1B Run indication
Bit2 HS2-P1A Run indication
Bit3 HS2-P1B Run indication
Bit4 HS3-P1A Run indication
Bit5 HS3-P1B Run indication
Bit6 HW1-P1 Run indication
Bit7 HWB-P1 Run indication
Bit8 Frequency converter Run indication
Bits9…15 not used
nvoDoValue SNVT_state Bit0 Output signal Do1
Bit1 Output signal Do2
Bit2 Output signal Do3
Bit3 Output signal Do4
Bit4 Output signal Do5
Bit5 Output signal Do6
Bit6 Output signal Do7
Bits7…15 not used
nvoAlarm
SNVT_state_64
Bit0 Run error P1A-HS1
Bit1 Run error P1B-HS1
Bit2 Run error P1A-HS2
Bit3 Run error P1B-HS2
Bit4 Run error P1A-HS3
Bit5 Run error P1B-HS3
Bit6 Run error P1-Hot water 1
Bit7 Run error P1-Storage tank
Bit8 Run error frequency converter
Bit9 Expansion vessel alarm
Bit10 External alarm
Bit11 Alarm, Boiler
Bit12 HS1 control error
Bit13 HS2 control error
Bit14 HS3 control error
Bit15 HW1 control error
Bit16 HW2 control error
Bit17 Sensor error
Bit17 Sensor error outdoor temperature (4)
Bit18 High supply temp. HW1
Bit19 High supply temp. Boiler
Bit21 Low supply temp. Boiler
Bit22 Pulse error, volume pulse
Bit23 Pulse error, energy pulse
Bit24 High 24 hour usage Cold water
Bit25 High energy consumption
Bit24 High hour usage Cold water
Bit27 Leakage
Bit28 Run error P1A&B-HS1