Argus RC InstSV FR
INSTRUCTION
i
Read this instruction before installation
and wiring of the product
ARGUS-RC
1
ARGUS-RC
Room controller
Argus-RC is a room controller from the Argus series, intended to con-
trol heating and cooling in a zone control system. Installation is directly
on the wall or on an electrical connection box. The controller does not
have a communication connection.
Technical data
Supply voltage 18...30 V AC, 50...60 Hz
Internal consumption 2.5 VA
Ambient temperature 0...50°C (32...122°F)
Ambient humidity Max 90% RH
Storage temperature -20...+70°C (-4...158°F)
Built-in temperature sensor NTC Type, range 0...50°C (32...122°F),
accuracy +/-0.5°C (+/-9°F) at 15...30°C
(59... 86°F)
Inputs and outputs Refer to connection illustrations and table
below
Connection terminals Lift type for cable cross-section 2.1 mm
2
(0,003 sq.in)
Protection class IP20
Material, casing Polycarbonate, PC
Weight 110 g (0,24 lbs)
Dimensions 95 x 95 x 31 mm (3,7 x 3,7 x 1,2 in)
LED
Setpoint knob
Installation
Place the controller in a location that has a temperature representative for
the room. A suitable location is approx. 1.6 m (5,2 ft) above oor level in a
place with unobstructed air circulation.
Remove the frame by depressing the locking tab in the lower edge of the
cover with a screwdriver. See gure 1.
Then pry out the electronics cassette using the four rectangular screwdri-
ver slots and levering against the edge of the bottom plate. See gure 2.
Note: Take care not to damage the electronics when inserting the screw-
driver into the slots.
Figure 1 Figure 2
The bottom plate with terminals has a number of xing hole combina-
tions. Select suitable holes (see gure 3) and screw the bottom plate onto
the wall or connection box, so that the arrows on the bottom plate point
upwards. Do not tighten the screws too hard!
With surface-mounted cabling, break-out suitable holes from the marks in
the plastic.
Figure 3. Bottom plate with mounting alternatives and location of
terminals, dimensions in mm (in).
68 (2,7)
60
Figure 4. Connection diagram for Argus-RC
30
31
32
33
°C
°C
+
-
24 V AC
40
41
42
43
20
21
22
23
24
10
11
12
13
14
+C
AGnd
-
-
AI1
UI1
DI1
DI2/CI
G
G0
DO1
-
-
GDO
G0
-
UO1
UO2
G0
G
G
G0
Y
G
G0
Y
Figure 5. Alternative connection for terminals 31, UI1, and terminal
33, DI2/CI, terminal 23, UO1, and terminal 24, UO2.
+
-
30
31
32
33
40
41
42
43
20
21
22
23
24
10
11
12
13
14
+C
AGnd
-
-
AI1
UI1
DI1
DI2/CI
G
G0
DO1
-
-
GDO
G0
-
UO1
UO2
EN
8316E
JUL 13
(2,4)