INSTALLATION OPERATION AND MAINTENANCE INSTRUCTION KBT002
Table Of Contents
- 1Introduction
- 2Safety
- 3Transportation and storage
- 4Installation
- 5Electrical connection
- 6Commissioning
- 7Operation
- 8Maintenance
- 9Troubleshooting
- 10Disposal
- 11Warranty
- 12Technical data
- 13Accessory overview
- 14EU Declaration of Conformity
- 15UK Declaration of Conformity
4.2 To install the product
1 Install the product on the mounting feet. Make sure that
the weight of the product is equal on the mounting feet.
Make sure the drain plug is at the lowest point of the
product to drain the condensation.
Caution
Risk of damage to the product if there is
much water that cannot drain.
2 If wall brackets are used, install the wall brackets.
Note:
Wall brackets for installation on walls are available as
accessories.
4.2.1 To connect the ducts to the
product
1 Put the ducts on the duct connections of the product.
Note:
Systemair recommends to use flexible connections or FK
fast clamps to attach the duct to the product. Flexible con-
nections and FK fast clamps are available as accessories.
2 Tighten the fast clamps around the duct and the product
with the screws that are supplied with the fast clamps.
Make sure that there is a distance between the duct and
the product to decrease vibrations transmitted from the
product to the duct system.
3 If you install the product near a duct bend, do these
steps to prevent vibrations, unwanted noise and de-
creased air pressure:
a. Measure the distance (A) between the product and
the duct bend.
b. Make sure that the distance (A) is a minimum of 2.5
x the diameter (B) of the duct system. For circular
ducts, (B) is the nominal diameter. For rectangular
ducts, (B) is the hydraulic diameter.
AA
B
5