Topvex FC2015 03
Topvex FC
|
7
Supply
Topvex FC06
Extract
Topvex FC06
SFP = Specic Fan Power (kW/m
3
/s)
The SFP value stated applies to the complete unit.
Thermal efciency
With air ratio 1:1 and according to EN308.
Sound data
The sound data tables indicate the sound power
level L
wA
, which should not be confused with the
sound pressure level.
0 0.2 0.4 0.6 0.8 11.2 1.4
0
100
200
300
400
500
600
Q [m³/s]
Ps [Pa]
0 1000 2000 3000 4000 5000
Q [m³/h]
15168/15169
SFP(1.5)
SFP(2.5)
SFP(2)
D
C
B
A
Topvex FC06
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6
0
100
200
300
400
500
Q [m³/s]
Ps [Pa]
0 1000 2000 3000 4000 5000
Q [m³/h]
15168/15169
D
C
B
A
Topvex FC06
η
90
85
80
75
0 0.2 0.4 0.6 0.8 1 1.21.4 1.
6
Q [m³/s]
0 1000 2000 3000 4000 5000
Supply
Sound power (L
w
), dB(A) – Mid-frequency band, Hz
Step Tot 63 125 250 500 1k 2k 4k 8k
A 10V 100 83 80 94 94 95 92 87 80
B 7,5V 92 74 74 87 84 87 84 78 71
C 5,3V 81 61 67 76 73 76 72 66 58
D 3,2V 64 49 56 56 55 59 54 47 37
Extract
Sound power (L
w
), dB(A) – Mid-frequency band, Hz
Step Tot 63 125 250 500 1k 2k 4k 8k
A 10V 76 67 68 73 70 64 57 48 41
B 7, 5 V 69 59 61 67 61 57 49 40 30
C 5,3V 62 50 59 56 50 45 39 28 22
D 3,2V 49 41 48 36 35 31 24 19 22
Surrounding
Sound power (L
w
), dB(A) – Mid-frequency band, Hz
Step Tot 63 125 250 500 1k 2k 4k 8k
A 10V 74 63 67 71 65 61 58 54 51
B 7,5V 68 56 61 66 55 53 50 45 42
C 5,3V 60 42 56 57 44 42 39 34 29
D 3,2V 45 30 44 36 27 26 22 17 15