Topvex FC2015 03

6
|
Topvex FC
Supply
Topvex FC04
Extract
Topvex FC04
SFP = Specic Fan Power (kW/m
3
/s)
The SFP value stated applies to the complete unit.
Thermal efciency
With air ratio 1:1 and according to EN308.
Sound data
The sound data tables indicate the sound power
level L
wA
, which should not be confused with the
sound pressure level.
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
0
100
200
300
400
500
600
Q [m³/s]
Ps [Pa]
0 500 1000 1500 2000 2500
Q [m³/h]
Topvex FC04
15416/15417
SFP 1,5
SFP 2,0
SFP 2,5
A
B
C
D
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
0
100
200
300
400
500
600
Q [m³/s]
Ps [Pa]
0 500 1000 1500 2000 2500
Q [m³/h]
A
Topvex FC04
15416/15417
B
C
D
η
90
85
80
75
0 500 1000 1500 2000 2500
0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8
Supply
Sound power (L
w
), dB(A) – Mid-frequency band, Hz
Step Tot 63 125 250 500 1k 2k 4k 8k
A 10V 92 66 71 87 84 86 83 77 72
B 6,7V 85 58 67 81 77 78 75 68 65
C 4,8V 77 50 73 68 66 69 66 58 52
D 2,6V 58 45 49 50 51 53 48 39 28
Extract
Sound power (L
w
), dB(A) – Mid-frequency band, Hz
Step Tot 63 125 250 500 1k 2k 4k 8k
A 10V 69 60 62 66 60 56 49 42 34
B 6,7V 65 53 58 63 53 50 42 34 27
C 4,8V 60 47 59 48 43 41 34 24 22
D 2,6V 47 43 44 32 30 26 18 18 21
Surrounding
Sound power (L
w
), dB(A) – Mid-frequency band, Hz
Step Tot 63 125 250 500 1k 2k 4k 8k
A 10V 67 56 58 66 55 53 50 46 42
B 6,7V 65 45 54 65 48 46 43 38 35
C 4,8V 60 38 60 50 38 37 33 28 24
D 2,6V 41 36 37 33 23 21 17 19 21