Topvex FC2015 03
Topvex FC
|
5
Performance
Supply
Topvex FC02
Extract
Topvex FC02
SFP = Specic Fan Power (kW/m
3
/s)
The SFP value stated applies to the complete unit.
Thermal efciency
With air ratio 1:1 and according to EN308.
Sound data
The sound data tables indicate the sound power
level L
wA
, which should not be confused with the
sound pressure level.
0 0.1 0.2 0.
30
.4
0
100
200
300
400
500
600
0 400 800 1200 1600
Q [m³/s]
Ps [Pa]
Q [m³/h]
15329/15331
Topvex FC02
A
B
C
D
η
90
85
80
75
0 400 800 1200 1600
0 0,1 0,2 0,3 0,4
Supply
Sound power (L
w
), dB(A) – Mid-frequency band, Hz
Step Tot 63 125 250 500 1k 2k 4k 8k
A 10V 89 63 68 75 85 82 83 77 76
B 6,7V 84 62 63 81 75 75 76 72 68
C 4,9V 74 52 58 67 66 67 69 63 57
D 2,8V 59 46 52 51 50 52 52 38 28
Extract
Sound power (L
w
), dB(A) – Mid-frequency band, Hz
Step Tot 63 125 250 500 1k 2k 4k 8k
A 10V 64 53 54 54 60 58 52 39 26
B 6,7V 60 56 50 50 52 52 46 34 22
C 4,9V 51 42 44 47 43 44 37 27 21
D 2,8V 41 35 37 31 30 30 22 17 21
Surrounding
Sound power (L
w
), dB(A) – Mid-frequency band, Hz
Step Tot 63 125 250 500 1k 2k 4k 8k
A 10V 66 41 52 53 65 51 50 44 39
B 6,7V 59 41 47 56 54 45 44 39 32
C 4,9V 51 30 42 47 46 36 37 31 23
D 2,8V 38 24 36 31 30 22 20 16 19
0 0.1 0.2 0.30.4
0
200
300
100
400
500
600
0 400 800 1200 1600
Q [m³/s]
Ps [Pa]
Q [m³/h]
15329/15331
A
B
C
D
SFP 2,5
SFP 2,0
SFP 1,5
Topvex FC02