TOPVEX FC OPERATING MAINTENANCE 125918A003
Table Of Contents
- 1 Warnings
- 2 Product Description
- 3 Interface Description
- 4 Commissioning
- 5 Maintenance
- 5.1 Important
- 5.2 Maintenance intervals
- 5.3 Maintenance instructions
- 5.3.1 Open the doors
- 5.3.2 Changing Supply/Extract air filter
- 5.3.3 Checking the heat exchanger
- 5.3.4 Checking the fans
- 5.3.5 Checking the Hot water heating battery
- 5.3.6 Checking the Electrical heating battery
- 5.3.7 Cleaning the extract louvers and inlet diffusers
- 5.3.8 Checking the outdoor air intake
- 5.3.9 Checking the duct system
- 5.3.10 Changing the Internal Battery
- 6 Troubleshooting
- 7 Service
Commissioning
|
13
MMaaiinn mmeennuu iitteemm
SSuubb--mmeennuu iitteemm 11 SSuubb--mmeennuu iitteemm 22 EExxppllaannaattiioonnss
→ Holidays Holidays (mm:dd)
1:01–01 — 01–02
2:01–01 — 01–01
3:01–01 — 01–01
Set up to 24 separate possible
holiday periods for a full year.
A holiday period can be any number
of consecutive days from one and
upwards.
The dates are in the format: MM:
DD.
When the current date falls within a
holiday period, the scheduler will
use the settings for the weekday
“Holiday”.
→ Manual/Auto
In this menu the running mode of all
the configured output signals and a
number of control functions can be
manually controlled.
The supply air controller's output
signal can be manually set
(Manual/Auto) to any value
between 0 and 100%. The
temperature output signals will
change accordingly if they are in
Auto mode. It is also possible to
manually control each of the
temperature output signals
individually.
SSiinnccee lleeaavviinngg aannyy ooff tthhee oouuttppuuttss
iinn mmaannuuaall ccoonnttrrooll wwiillll ddiissrruupptt tthhee
nnoorrmmaall ccoonnttrrooll,, aann aallaarrmm wwiillll bbee
ggeenneerraatteedd aass ssoooonn aass aannyy oouuttppuutt
iiss sseett ttoo aa mmaannuuaall mmooddee..
Supply temp.
contr.
Auto
Manual set: 0.0
Set the supply air temperature
controller to Auto, Manual or Off.
Set the output signal between 0-
100%.
The outputs Y1, Y2 and Y3, if in
Auto-mode, will follow the signal
according to the set split values.
SAF: Auto
Manual set: 0.0
Set the output signal for SAF
(supply air fan) to:Auto,
Manual,1/2–speed or 1/1–
speed.
EAF: Auto
Manual set: 0.0
Set the output signal for EAF
(extract air fan) to:Auto,
Manual,1/2–speed or 1/1–
speed.
Heating
Auto
Manual set: 100.0
Set the heating to Auto, Manual or
Off.
Set the manual output 0-100%.
Exchanger
Auto
Manual set: 0.0
Set the exchanger rotor control to
Auto, Manual or Off
Set the manual output 0-100%
Cooling
Auto
Manual set: 0.0
Set the cooling to Auto, Manual or
Off
Set the manual output 0-100%
Note:
NNeeeeddss ttoo bbee aaccttiivvaatteedd iinn
oorrddeerr ttoo bbee vviissiibbllee hheerree
P1–Heating
Auto
Set the pump control for the
heating coil to Auto, On or Off