TOPVEX FC OPERATING MAINTENANCE 125918A003

Commissioning
|
11
MMaaiinn mmeennuu iitteemm
SSuubb--mmeennuu iitteemm 11 SSuubb--mmeennuu iitteemm 22 EExxppllaannaattiioonnss
Outdoor comp.Setp.
–20°C = 0 m³/h
0°C = 0 m³/h
Act. Comp: 0 m³/h
Set the SAF airflow compensation
for the settable outdoor
temperature. The outdoor
compensation is linear and is set
using two parameter pairs which
give the value of the compensation
at two different outdoor
temperatures. The compensation
can be positive or negative.
Shows the actual airflow
compensation.
Flow control EAF
Actual: xxx m³/h
Setp.:xxx m³/h
Airflow for the extract air fan
(constant airflow control).
OOnnllyy vviissiibbllee iiff tthhee uunniitt iiss
ccoonnffiigguurreedd ffoorr FFllooww ccoonnttrrooll
((CCAAVV))..
Flow control EAF
Setp 1/1: 1100 m³/h
Setp 1/2: 550 m³/h
Set the normal (1/1) and reduced
(1/2) airflow for the extract air fan.
Outdoor comp.Setp.
–20°C = 0 m³/h
0°C = 0 m³/h
Act. Comp: 0 m³/h
Set the EAF airflow compensation
for the settable outdoor
temperature. The outdoor
compensation is linear and is set
using two parameter pairs which
give the value of the compensation
at two different outdoor
temperatures. The compensation
can be positive or negative.
Shows the actual airflow
compensation.
Pressure control
SAF
Actual: Pa
Setp.: Pa
The actual external pressure and set
point for the supply air fan.
OOnnllyy vviissiibbllee iiff tthhee uunniitt iiss
ccoonnffiigguurreedd ffoorr ""PPrreessssuurree ccoonnttrrooll""
((VVAAVV))
Pressure control
SAF
Setp 1/1: 200 Pa
Setp 1/2: 100 Pa
Set the external pressure set point
for normal speed (1/1) and reduced
speed (1/2) for the supply air fan.
Outdoor comp.Setp.
1
—20°C = 0 Pa
10°C = 0 Pa
Act. Comp: 0 Pa
Set the SAF pressure compensation
for the settable outdoor
temperature. The outdoor
compensation is linear and is set
using two parameter pairs which
give the value of the compensation
at two different outdoor
temperatures. The compensation
can be positive or negative.
Shows the actual pressure
compensation.
Pressure control
EAF
Actual: Pa
Setp.: Pa
The actual external pressure and set
point for the extract air fan.
OOnnllyy vviissiibbllee iiff tthhee uunniitt iiss
ccoonnffiigguurreedd ffoorr ""PPrreessssuurree ccoonnttrrooll""
((VVAAVV))..
Pressure control
EAF
Setp 1/1: 200 Pa
Setp 1/2: 100 Pa
Set the external pressure set point
for normal speed (1/1) and reduced
speed (1/2) for the supply air fan.
125918 | A003