TOPVEX FC OPERATING MAINTENANCE 125918A003

10
|
Commissioning
MMaaiinn mmeennuu iitteemm
SSuubb--mmeennuu iitteemm 11 SSuubb--mmeennuu iitteemm 22 EExxppllaannaattiioonnss
Efficiency
exch.
Actual: %
Output exchanger
Actual: 100%
Actual heat recovery efficiency.
The function calculates the heat
exchangers temperature efficiency
in % when the output signal to the
exchanger is higher than 5% and
the outdoor temperature is lower
than 10° C.
Efficiency calculated from the
Outdoor, Extract and Efficiency air
temperature.
When the control signal is lower
than 5% or the outdoor
temperature is higher than 10° C
the display will show 0%.
Status of the exchanger output.
Temp for
calculation
efficiency
Act: NaN C
Presented temperature for supply
air efficiency calculation.
Air Control
TThhiiss mmeennuu ooppttiioonn bbeeccoommeess
vviissiibbllee iiff tthhee uunniitt iiss ccoonnffiigguurreedd ffoorr
FFllooww ccoonnttrrooll”,, MMaannuuaall
ffrreeqquueennccyy” oorr PPrreessssuurree ccoonnttrrooll..
Frequency control
manual SAF
Output: %
Frequency control manual.
Fans controlled by setting fixed
output signal.
TThhiiss mmeennuu ooppttiioonn bbeeccoommeess
vviissiibbllee iiff tthhee uunniitt iiss ccoonnffiigguurreedd ffoorr
""MMaannuuaall ffrreeqquueennccyy”..
Frequency control
manual SAF
Output 1/1: 75%
Output 1/2: 50%
Outdoor comp.
output.
–20°C = 0 m³/h
0°C = 0 m³/h
Act. Comp: 0 m³/h
Frequency control
manual EAF
Output: %
Frequency control
manual EAF
Output 1/1: 75%
Output 1/2: 50%
Outdoor comp.
output.
–20°C = 0 m³/h
0°C = 0 m³/h
Act. Comp: 0 m³/h
Flow control SAF
Actual: m³/h
Setp.: m³/h
Airflow for the supply air fan
(constant airflow control).
OOnnllyy vviissiibbllee iiff tthhee uunniitt iiss
ccoonnffiigguurreedd ffoorr FFllooww ccoonnttrrooll
((CCAAVV))..
Flow control SAF
Setp 1/1: 1100 m³/h
Setp 1/2: 550 m³/h
Set the normal (1/1) and reduced
(1/2) airflow for the supply air fan.
125918 | A003