Commissioning
• Outdoor air intake is positioned with sufficient distance to pollution sources (kitchen ventilator exhaust, central vac-
uum system exhaust or similar)
• All external equipment are connected
• The following data is available:
• Intended configuration, for example temperature control functions, fan control, external control functions etc.
• How the unit is supposed to operate according to a weekly schedule (normal and reduced speed)
4.2 Initial setup of the unit
On the first start-up, the controller will start a special program for setting language, supply air temp set point, Time &
date and week schedule for normal speed. Use the “OK” button to move between changeable parameters and the UP/
DOWN arrows to see the displayed alternatives. Confirm by pressing “OK” once more. Move on down in the menu
structure by use of the UP/DOWN arrows.
The following will be displayed:
Choose Language
English
11 Select language by pressing “OK” and then move be-
tween the alternatives with the UP/DOWN buttons.
Confirm by pressing “OK”. Move to the next level by
pressing the “DOWN” button.
Extract air temp
Actual:.... ºC
Setp.: 18 ºC
22 Shows the actual extract air temperature
Set the extract air set point. Default is 18°C (logon to
service level needed, code 2222, to change default
setting)
Time: 12.46
Date: 2010–03–12
Weekday: Friday
33 Check and make sure that correct time and date is dis-
played, if not change the settings
44 Set 00:00 - 24:00 for continuous running. Setting
00:00 - 00:00 inactivates the period (stops the unit).
Normal speed overrides Reduced speed i.e. Normal
speed 07:00 - 16:00 and Reduced speed 00:00 -
24:00 runs the unit on Normal speed 07:00 - 16:00
and Reduced speed the rest of the day.
Normal speed
Monday → Friday
Per 1: 07:00 – 16:00
Per 2: 00:00 – 00:00
55 Set the week schedule for how it’s intended for the
unit to operate at normal speed during Monday to Fri-
day. It’s possible to set 2 periods per day.
Normal speed
Saturday → Holiday
Per 1: 00:00 – 00:00
Per 2: 00:00 – 00:00
66 Set the week schedule for how it’s intended for the
unit to operate at normal speed during Saturdays and
holidays. It’s possible to set 2 periods per day.
Reduced speed
Monday → Friday
Per 1: 00:00 – 00:00
Per 2: 00:00 – 00:00
77 Set the week schedule for how it’s intended for the
unit to operate at reduced speed during Monday to
Friday. It’s possible to set 2 periods per day
Reduced speed
Saturday → Holiday
Per 1: 00:00 – 00:00
Per 2: 00:00 – 00:00
88 Set the week schedule for how it’s intended for the
unit to operate at reduced speed during Saturdays
and holidays. It’s possible to set 2 periods per day.
End Wizard
No
99 Select “Yes” or “No”
After finishing the setup the menu system for “Operator level” will be available.
125918 | A003