15
4.7 Connections
4.7.1 Ducting
4.7.1.1 Air connections principles
Fig. 8 Connections and basic components in right hand connected units
PPoossiittiioonn DDeessccrriippttiioonn
SSyymmbbooll
A
Connection supply air
B
Connection exhaust air
C
Connection outdoor air
D Connection extract air
1
Fan supply air
2 Fan extract air
3
Filter supply air
4
Filter extract air
5
Heat exchanger
6
Electrical connection box
7
Damper by-pass outdoor air
8
Pressure transmitter fans (accessory)
9
Pressure guard filter
10
Re-heater battery
11
Manual over heat protection reset (EL units)
12
Differential pressure sensor – airflow
13
Differential pressure sensor – deicing
4.7.1.2 Condensation and Heat Insulation
Outdoor air duct and discharge ducts must always be well insulated against condensation. Correct insulation installation
on ducts connected to the unit is especially important. All ducts installed in cold rooms/areas must be well insulated.
Use insulating covering (minimum 100 mm mineral wool) with plastic diffusion barrier. In areas with extremely low out-
door temperatures during the winter, additional insulation must be installed. Total insulation thickness must be at least
150 mm.