TOPVEX FC INSTALLATION INSTRUCTION 125917 CE A006

Installation |
7
4 Installation
Topvex FC is designed for installation in false ceilings.
4.1 Unpacking
Verify that all ordered equipment are delivered before starting the installation. Any deviation from the ordered equip-
ment must be reported to the supplier of Systemair products.
4.2 Where/how to install
Topvex FC are meant for indoor installation. The electronic components should not be exposed to lower temperature
than C and higher than +50° C.
Topvex FC must always be installed horizontally with the inspection doors downwards.
When choosing the location it should be kept in mind that the unit requires maintenance regularly and that the inspec-
tion doors should be easily accessible. Leave free space for opening the doors and for taking out the main components
(chapter 3.2.1.1.)
Note:
If there is not sufficient space to open the inspection doors, it is possible to mount rails and use existing
doors as sliding doors (accessory) chapter 4.6.
The outdoor air intake of the building should if possible be put in the northern or eastern side of the building and away
from other exhaust outlets like kitchen fan outcasts or laundry room outlets.
Warning
The door handles are only intended to be used during the installation and service. Handles must be
removed before the unit is put into operation to ensure the required level of safety for the unit.
The unit must be duct connected or in some other way provided with protection so that it is not possible
to come in contact with the fans through the duct connections
Caution
Do not lift the unit in the mounting brackets. Only intended for mounting in roof.
125917 | A006