CORRIGO VENTILATION 3.6 MANU

Table Of Contents
Manual Corrigo Ventilation, revision V Chapter 17 Configuration 99
If a sensor is configured in the intake duct (”intaketemp”) this temperature will be compared with the
outdoor temperature. If the temperature in the intake duct does not exceed the outdoor temperature
by more than 1°C (adjustable) 5 minutes (fixed) after start-up when using preheating, preheating will
be aborted. The same conditions apply to precooling, i.e. if the intake temperature is not more than
1°C (adjustable) cooler than the outdoor temperature, precooling will be aborted.
Pretreatment always starts at start-up of the unit, if the outdoor temperature so permits. If pretreatment
is aborted due to a small difference between the intake temperature and the outdoor temperature,
pretreatment will be blocked for 6 hours. Then pretreatment will start (if the outdoor temperature so
permits) and run for at least 5 minutes.
Outdoor temp for
activating
preheating: 8.0 °C
precooling: 19.0 °C
Minimum diff
outdoor temp-
intaketemp: 1.0 °C
17.28 Alarm setting
Permits configuration of all alarms.
Select the appropriate alarm number from the alarm list below. The alarm text for the alarm will be
displayed and the alarm priority can be set; "A-alarm", "B-alarm", "C-alarm” or “Not active". The
device can be stopped via “Extra stop function” or, optionally, be made to run at reduced speed during
an alarm (only configured using E tool
©
).
Malfunction supply air
fan
Priority: B-alarm
Extra stop function
Active