96 Chapter 17 Configuration Manual Corrigo Ventilation, revision V
17.23 Actuator type
Choose output signals to the actuators connected to the analogue control outputs: 0…10 V DC, 2…10
V DC, 10…0 V DC or 10…2 V DC.
Actuator type
Y1 heating: 0-10V
Y2 exchan: 0-10V
Y3 cooling: 0-10V
Actuator type
SAF: 0-10V
EAF: 0-10V
Split: 0-10V
Actuator type
Humidity: 0-10V
Extra unit: 0-10V
Y1 heat/Y3 cool 0-10V
Actuator type
Y4 extra seq: 0-10V
Actuator type
Y5 extra seq: 0-10V
NOTE: Even though many manufacturers state 0…10 V DC as control signal for many actuators, the
actual control signal is more often than not 2…10 V DC. Check the actuator documentation carefully.
If uncertain, choose 0…10 V DC. Although control might be less accurate, it will ensure that the
valve always can be driven to its fully opened and fully closed positions.
17.24 Running time, 3-position actuators
These parameters have no function if analogue actuators are configured.
The values are used to determine the control parameters for 3-position actuators.
It is important to set correct values since incorrect values lead to sloppy control.
Actuator run time
Heating: 255 s
Exchanger: 255 s
Cooling: 255 s
17.25 Step controllers
Step contr heating
Step contr cooling
17.25.1 Step controller heating
Step controller heating can be set to sequential or binary.
Step contr. heating
Sequential
Binary steps