94 Chapter 17 Configuration Manual Corrigo Ventilation, revision V
Running timeis the time the damper actuator needs to open or close. Hour for exerciseis the hour
of the day at which you want the function to be run.
For detailed description of damper exercising, see the section Damper control.
It is possible to select whether the outdoor damper should remain open or closed during an eventual
fire. For the damper to remain open during fires, the running mode must be set to a setting other than
“Stopped”.
Outdoor air damper
when fire
Always open
17.16 Humidity control
Humidity control can be configured as either humidification or dehumidification or as combined
humidification/dehumidification.
These settings are for the digital output "Humidification/Dehumidification".
Humidity control
Humid-/Dehumidificat
Start limit: 15%
Stop limit: 5%
For a detailed description, see the section Humidity control.
17.17 Exchanger deicing
Exchanger deicing
Yes
Deicing parameters
Setp deicing:-3.0°C
Hysteresis: 1.0 °C
Stop temp SAF:-10.0 °
Min. run time: 5 min
For detailed description of exchanger alternatives, see section 5.1.3 Heat exchanger.
17.18 Cooling recovery
Cooling recovery
Off
Cooling limit: 0.0°C
Cooling limit is the difference in temperature between extract air and outdoor air.
For details, see section 5.1.7 Cooling recovery.
17.19 Minimum limit dampers
Min limit dampers
Not active
Min limit.: 5%
For detailed description of exchanger alternatives, see section 5.1.3 Heat exchanger.