CORRIGO VENTILATION 3.6 MANU

Table Of Contents
92 Chapter 17 Configuration Manual Corrigo Ventilation, revision V
P1 Heating
Pump stop: Yes
Stop delay: 5 min
Outd temp stop 10 °C
Differential: 1.0
P1 Exchanger
P1 exchanger
Stop delay: 5 min
P1 Cooling
P1 cooling
Stop delay: 5 min
For a detailed description of pump functions, see the section Pump control.
17.12 Free cooling
Free cool active:Yes
Outd temp activation
22.0°C
Outd temp night
High: 18.0 °C
Low: 10.0 °C
Room temp min 18.0°C
Hour for start/stop
free cooling
Start: 0
Stop: 7
Time to block heat
output after
free cooling
60 min
Fan setpoint offset
when free cooling
SAF: 0
EAF: 0
Outdoor sensor
placed in intake
channel
No
For detailed description, see section 5.1.6 Free cooling.
17.13 Support control
Note: If you select the function support control without EAF (extract air fan), a recirculation damper
must be used. See more in section 5.1.5.