Manual Corrigo Ventilation, revision V Chapter 15 Settings 81
Alarm delay control
dev pressure
SAF: 30 min
EAF: 30 min
Alarm delay, Humidity
Alarm delay control
deviation humidity
30 min
Alarm delay, exchanger efficiency
Low efficiency
30 min
Alarm delay, fan malfunction (SAF and EAF)
Alarm delay
malfunction
SAF: 120 s
EAF: 120 s
Alarm delay, pump malfunction
Alarm delay malfunc
P1 heating: 5 s
P1 cooling: 5 s
P1 exchan: 20 s
Alarm delay, misc.
Filter guard1: 180 s
Filter guard2: 180 s
Flow switch: 5 s
Frost prot: 0 s
Ext. Frost prot. DI refers to the digital input signal De-icing Heat exchanger.
Alarm delay, misc. 2
Alarm delay
Deicing DI: 0 s
Fire alarm: 0 s
Ext alarm: 0 s
Frost protection DI refers to the digital input signal De-icing thermostat exchanger.
Alarm delay, misc. 3
Alarm delay
Elec. heat: 0 s
Sensor error: 5 s
Rot sent exch: 20 s
15.7.3 Restore alarm
Service alarm
(Filter alarm)
Time counter set
to zero: No