80 Chapter 15 Settings Manual Corrigo Ventilation, revision V
Al lim room air
High temp: 30.0 °C
Low temp: 10.0 °C
Alarm limit frost protection
Alarm limit frost
protection
7.0 °C
Alarm limit, pressure
Control dev SAF
40.0 Pa
Control dev EAF
40.0 Pa
Alarm limit Humidity
Control deviation
humidity: 10 %
Alarm limit, exchanger efficiency
Low efficiency
50.0 %
Service alarm filter
Service alarm
(Filter alarm)
Time until alarm
activates: 0 month
15.7.2 Alarm delays
Alarm delay, supply air
Al del supply air
Control dev: 30 min
High temp: 5 s
Low temp: 5 s
Alarm delay, extract air
Al del extract air
High temp: 30.0 min
Low temp: 30.0 min
Alarm delay, room
Al. del. room air
High temp: 30.0 min
Low temp: 30.0 min
Alarm delay, frost protection
Alarm delay
Frost prot.: 0 s
Frost risk: 0 s
Alarm delay control SAF and EAF