78 Chapter 15 Settings Manual Corrigo Ventilation, revision V
Shutdown mode
Shutdown mode
P-band: 100.0 °C
I-time: 100 s
Frost protection control
Frost protection
Frost protection
Active
Setp shutdown: 25°C
P-band active: 5°C
Fast stop at frost-
protection alarm
Yes
"Setp shutdown" is the shutdown mode setpoint.
P-band active 5°C means that the frost protection controller will start overriding the heating output
when the frost protection temperature is less than five degrees above the set frost alarm limit. The
default alarm limit is 7°C. It can be changed in the menu Settings/Alarm settings/Alarm limits/Alarm
limit frost protection.
Sequence with
frost prot
Y5 extra sequence
Y1, Y4 Extra sequence and Y5 Extra sequence can be used for frost protection control.
Exchanger deicing
Deicing
P-band: 100 °C
I-time: 100 s
15.2 Control pressure
Pressure control SAF
Pressure control SAF
P-band: 500 Pa
I-time: 60 s
Min.output: 0 %
Pressure control EAF
Pressure contr EAF
P-band: 500 Pa
I-time: 60 s
Min.output: 0 %