Manual Corrigo Ventilation, revision V Chapter 10 Temperature 65
In control mode 8, the extract air setpoint is compensated based on outdoor temperature. Note that
the curve must be adjusted for optimal functionality.
Both the outdoor and extract air temperature are changeable for the curve.
Support control heating
Support heating
Room temp for
Start: 15.0°C
Stop: 21.0°C
Support control cooling
Support cooling
Room temp for
Start: 30.0°C
Stop: 28.0°C
Frost protection temperature
Frost protection
Actual: 30.9°C
Deicing exchanger
Deicing exchanger
Actual: 11.2°C
Setp: -3.0°C
Hysteresis: 1.0°C
Heat exchanger efficiency monitoring
Efficiency exch
Actual: 93%
Output exchanger
Actual: 100%
Recirculation (see 5.1.11)
Temp.setpoint when
recirc. (Supply/
Extract/Room)
18.0°C
Offset SAF when
frequency control
and recirculation
0.0 Pa
"Offset SAF" makes it possible to add an offset to the setpoint during normal operation. If pressure
control has been configured, offset is entered in Pa or inch of water gauge (in.wg.). A factor (x100)
is used in both the program and display when the unit “in.wg.” has been selected.
During flow control, it is set in m
3
/h and during manual control in percent (%).
Extra unit (see 5.2)
Extra unit
Actual: 21.2°C
Setp: 20.0°C
Enthalpy control
Enthalpy indoors
33.8 kJ/Kg
Enthalpy outdoors
35.0 kJ/Kg