64 Chapter 10 Temperature Manual Corrigo Ventilation, revision V
Control mode 7: Outdoor temperature compensated room control.
Room temp1
Actual: 22.0°C
Setp: 21.5°C
Outdoor comp setp
-20.0°C = 25.0°C
-15.0°C = 24.0°C
-10.0°C = 23.0°C
Outdoor comp setp
-5.0°C = 23.0°C
0.0°C = 22.0°C
5.0°C = 20.0°C
Outdoor comp setp
10.0°C = 18.0°C
15.0°C = 18.0°C
If cascade control
max/min supply setp
Max: 30.0°C
Min: 12.0°C
In control mode seven, the room setpoint is compensated based on outdoor temperature. Note that the
curve must be reset for optimum functionality.
Both the outdoor and room temperature are changeable for the curve.
Control mode 8: Outdoor temperature compensated extract air control.
Extract air temp
Actual: 21.0°C
Setp: 21.1° C
Outdoor comp setp
-20.0°C = 25.0°C
-15.0°C = 24.0°C
-10.0°C = 23.0°C
Outdoor comp setp
-5.0°C = 23.0°C
0.0°C = 22.0°C
5.0°C = 20.0°C
Outdoor comp setp
10.0°C = 18.0°C
15.0°C = 18.0°C
If cascade control
max/min supply setp
Max: 30.0°C
Min: 12.0°C