CORRIGO VENTILATION 3.6 MANU
Table Of Contents
50 Chapter 5 Functional description Manual Corrigo Ventilation, revision V
5.4.3 Extra control for external motor
External control of an external (fan) motor can be configured. The fan is started via either a digital
input or a time channel.
A digital output activates the (fan) motor. A digital input is available for run time indication/motor
protection.
Inputs and outputs
DI
Motor control 1
DI
Motor control 1 indication
DI
Motor control 2
DI
Motor control 2 indication
DO
Motor control 1 start
DO
Motor control 2 start
5.5 Pump control
Digital inputs and outputs can be configured for pump control.
All the pumps can use run indication with malfunction alarm or an alarm input connected to a motor
protection or similar.
5.5.1 Heating circuit, water heating
The circulation pump for the heating circuit will always run when the outdoor temperature is lower
than a settable value (FS +10°C). At higher outdoor temperatures the pump will run when the output
signal “Y1 heating” or “Extra sequence Y4” is larger than 0 V.
If no outdoor temperature sensor has been configured, the stop temperature can be set to 0°C. Then
the pump will only run on heat demand.
The pump has a settable stop delay.
The pump will be exercised once daily at 3 p.m. for one minute or the set shortest running time,
whichever is the longest.
5.5.2 Exchanger circuit, liquid connected exchangers
The circulation pump for the exchanger circuit will run when the output signal “Y2 Exchanger” is
larger than 0 V.
The pump has a settable, shortest running time.
The pump will be exercised once daily at 3 p.m. for 1 minute, or the set stop delay, whichever is the
longest.
5.5.3 Cooling circuit
The circulation pump for the cooling circuit will run when the output signal “Y3 Cooling” is larger
than 0 V.
The pump has a settable, shortest running time.
The pump will be exercised once daily at 3 p.m. for 1 minute, or the set stop delay, whichever is the
longest.
Corrigo can be configured to block DX cooling if a ”Malfunction P1-Cooling” alarm should occur.