CORRIGO VENTILATION 3.6 MANU
Table Of Contents
Manual Corrigo Ventilation, revision V Chapter 3 Installation and wiring 17
Chapter 3 Installation and wiring
3.1 Installation
Corrigo can be mounted in a DIN-standard casing (minimum 9 modules), on a DIN-rail in a cabinet
or, using a suitable front-mounting kit, in a cabinet door or other control panel.
Ambient temperature: 0…50°C.
Humidity: Max. 90 % RH, non-condensing.
The picture below shows a wiring example for Corrigo E283W-3.
3.2.1 Supply voltage
24 V AC ±15%, 50…60 Hz or 21…36 V DC
If Corrigo and its connected actuators share the same transformer, it is essential that the same
transformer pole is used as reference for all the equipment. The equipment may otherwise not function
as intended and may also suffer damages.