2.2 Technical data
Protection class .................................................................................................................. IP20
Display ........................................................ 4 rows of 20 characters. Background illumination.
LEDs
Yellow ....................................................................................................... Settable parameter
Red................................................................................................................ Alarm indication
Clock .................................................................. Year base 24 hour clock with battery backup.
Automatic summer-/winter-time changeover.
Operating system .......................................................................................................... EXOreal
Supply voltage .................................................... 24 V AC ±15%, 50…60 Hz or 21…36 V DC
Power consumption ........................................ 5 VA, 3 W (DC), model …W: 9 VA, 5 W (DC)
Dimensions .................................................................... 148x123x60 (WxHxD incl. terminals)
Casing .......................................................................... Standard Euronorm (8.5 modules wide)
Mounting ................................................................................................................ On DIN-rail
Operation
Climatic conditions according to IEC 721-3-3 ........................................................ Class 3k5
Ambient temperature ................................................................................................. 0...50°C
Ambient humidity .............................................................................................. Max 95% RH
Mechanical requirements according to IEC721-3-3 .............................................. Class 3M3
Vibration .......................................................... IEC60068-2-6, Test FC, vibration Sinusoidal
Shock ................................................................................................ IEC60068-2-27, Test Ea
Transport
Climatic conditions according to IEC 721-3-2 ........................................................ Class 2k3
Ambient temperature .............................................................................................. -20...70°C
Ambient humidity .............................................................................................. Max 95% RH
Mechanical requirements according to IEC721-3-2 .............................................. Class 2M2
Vibration .......................................................... IEC60068-2-6, Test FC, vibration Sinusoidal
Shock ................................................................................................ IEC60068-2-27, Test Ea
Free fall .............................................................................................IEC60068-2-27, Test Ed
Storage
Climatic conditions according to IEC 721-3-1 ........................................................ Class 1k3
Ambient temperature .............................................................................................. -20...70°C
Ambient humidity .............................................................................................. Max 95% RH
Battery
Type .....................................................................................Replaceable Lithium cell, CR2032
Battery life ................................................................................................... Better than 5 years
Warning .................................................................................................... Low battery warning
Battery backup ............................................................................... Memory and real time clock
Communication
EXOline Port 1, insulated via a built-in RS485 contact.
EXOline Port 2, via a built-in RS485 contact.
EXOline TCP/IP.
Modbus communication via serial RS485 communication or TCP/IP.
Baudrate: 150, 300, 600, 1200, 2400, 4800, 9600
BACnet-AAC/IP via TCP/IP or BACnet-AAC MS/TP via RS485
Baudrate: 9600, 19200, 38400, 76800
Suitable model should be selected for appropriate needs.
EMC emission and immunity standard
This product conforms to the requirements of the EMC Directive 2004/108/EC through product
standards EN 61000-6-1 and EN 61000-6-3.
RoHS
This product conforms to the Directive 2011/65/EU of the European Parliament and of the Council.