Danfoss FC 101
Danfoss frequency converters are controlled via Modbus. Communication, alarms and certain
indications can be read.
The following signals can be read/written from/to the frequency converter:
Address Modbus register Name Scaling Type
3100 33100,43100 FB speed reference (SP) 100 %
50000
350000,450000
FB control word
-
16130 316130,416130 Motor frequency 10 Hz
16140 316140,416140 Current 100 A
16100 316100,416100 Output 1000 kW
16300
316300,416300
DC voltage
1
V
16030 316030,416030 Status change -
The variables presented in the display of the Corrigo are:
Frequency (Hz), Current (A), Output (kW), Accumulated power (kWh).
ECBlue
ECBlue frequency converters are controlled via Modbus. Communication, alarms and certain
indications can be read.
The following signals can be read/written from/to the frequency converter:
Address Modbus register Name Scaling Type
3
30003,40003
FB speed reference (SP)
1
%
5 30005,40005 FB control word - 0 = off
3 = on
15
30015,40015
RPM
Rpm
16 30016,40016 Current 100 A
34 30034,40034 Output 1 kW
21
30021,40021
DC voltage
1
V
13 30013,40013 Alarm - Error code