CORRIGO VENTILATION 3.6 MANU
Table Of Contents
LS iS7
The following signals can be read/written from/to the frequency converter:
Address Modbus register Name Scaling Type
5 30005,40005 FB speed reference (SP) 10 %
6
30006,40006
FB status word
-
Binary
10 30010,40010 Motor frequency 100 Hz
791 30791,40791 Torque 100 %
786
30786,40786
RPM
1
Rpm
784 30784,40784 Motor current 10 A
790 30790,40790 Output 10 kW
789 30789,40789 Voltage 10 V
14
30014,40014
Status change
-
Binary
816 30816,40816 Alarm - Binary
817 30817,40817 Alarm 2 - Binary
EBM-PAPST
EBM frequency converters are controlled via Modbus. Communication, alarms and certain indications
can be read.
The following signals can be read/written from/to the frequency converter:
Address Modbus register Name Scaling Type
53250 30250,40250 FB speed reference (SP) 640 %
53249 30249,40249 FB control word -
53265 30265,40265 RPM Rpm
53266
30226,40266
FB status word
-
Binary
53267 30267,40267 Status change Binary
53268 30268,40268 DC voltage V
53269
30269,40269
Motor current
A
The variables presented in the display of the Corrigo are:
Frequency (Hz), Current (A), Output (kW), Accumulated power (kWh).