CORRIGO VENTILATION 3.6 MANU

Table Of Contents
Appendix Frequency converters and EC
controllers for heat exchangers
Version 3.6 and later of Corrigo ventilation supports the frequency converters and/or EC controllers
for heat exchangers listed below:
Vacon NXL
Lenze
Omron V1000
Emerson Commander
LS
EBM
Danfoss FC 101
ABB ACS
EC Blue
Heat exchanger via Modbus:
RHC 200
VariMax25M
When communicating via frequency converters through Modbus, it is sometimes necessary to change
certain settings in the frequency converter.
Two parallel connected frequency converters for supply air and two parallel connected frequency
converters for extract air can be run. The supply air fan will have address 1 and the parallel supply air
fan address 3. The extract air fan will have address 2 and the parallel extract air fan address 4.
Below is described what settings are necessary in the various models:
Vacon NXL
No settings necessary. Vacon NXL frequency converters are controlled via Modbus. Communication,
alarms and certain indications can be read:
The following signals can be read/written from/to the frequency converter:
Address Modbus register Name Scaling Type
2003
32003, 42003
FB speed reference (SP)
1000
%
2001 32001, 42001 FB status word - Binary
11 30011, 40011 Acc. motor output 1 kW
80 30080, 40080 Number of decimals for acc. motor
output
1 kWh
2103 32103, 42103 FB motor speed 100 %
2105 32105, 42105 Motor speed 1 +/- Rpm
2106
32106, 42106
Current
100
A
2107 32107, 42107 Torque 10 +/- % (of nominal)
1501 31501, 41501 Output 1000 kW
2110
32110, 42110
Voltage DC
1
V
2111 32111, 42111 Alarm - Error code