112 Chapter 17 Configuration Manual Corrigo Ventilation, revision V
2004-08-15 11:28
System: Running
Sp:22.0°C Act:21.8°C
Y1:0% Y2:93% Y3:0%
Type 3
The first line shows the date and time.
The second line shows the present running status.
The third line shows the present temperature setpoint and actual values.
The fourth line shows the present SAF and EAF pressures.
15/03/2004 11:28
System: Running
Sp:22.0°C Act:21.8°C
SF:1100Pa EF:1050Pa
Type 4
The text on the first line can be changed using E tool
©
.
The second line shows the date and time.
The third line shows the present running status.
Vent unit 18 PX
2004-03-15 11:28
System: Running
Type 5
The text on the first line can be changed using E tool
©
.
The second line shows the date and time.
Vent unit 18 PX
2004-03-15 11:28
17.31.3 Automatic summer-/wintertime change-over
When Corrigo is set on automatic summertime/wintertime change-over, the timer will automatically
change between summertime and wintertime according to European standard.
Automatic summer/
winter time
change-over
Yes
17.31.4 Address
Corrigo uses the addresses below when connecting to E tool
©
, and when multiple controllers are
connected in an EXO network. E tool
©
normally uses the addresses below, so if an address is changed,
the new address must also be entered in E tool
©
. If several Corrigo are connected in a network, all the
units must have the same ELA address, but each unit must have a unique PLA address.
Address
PLA: 254
ELA: 254