CORRIGO VENTILATION 3.6 MANU

Table Of Contents
110 Chapter 17 Configuration Manual Corrigo Ventilation, revision V
Split settings
extra sequence Y4
0% at HCOut= 0%
100% at HCOut= 0%
Split settings
extra sequence Y5
0% at HCOut= 0%
100% at HCOut= 0%
17.30.7 Outdoor temp. for control mode change
If the unit is configured for combined Supply air/Room control this menu permits the setting of the
change-over outdoor temperature.
Outdoor temp for
control mode change
13.0°C
17.30.8 Split of optional temp. sequence
Any one of the analogue temperature control output sequences "Y1", "Y2" and "Y3", ”Y1 heating/Y3
cooling”, ”Y4-extra sequence” or ”Y5-extra sequence” can be split, for example to control two
heating valves in sequence. The split is always even, 50/50, which means that each part of the split
will have half the part of the P-band assigned to the output. An analogue output must be assigned to
the output signal “Split”. On increasing output demand, the regular output is always run first and then
the output that has been configured as Split.
Split optional
temperature sequence
Y1 Y2 Y3
No split
17.30.9 Fast stop on overheating
If this function is active, the fans will be immediately stopped when there is an overheating alarm,
regardless of the set cool-down time.