108 Chapter 17 Configuration Manual Corrigo Ventilation, revision V
Device ID
The ID of a device, used to identify it on the BACnet network. This number cannot be duplicated
anywhere on the BACnet network and must therefore be unique. To set an ID value of 34600, the
low number would be set to 4600 and the high number to 3.
Speed
Sets the communication speed of the MS/TP network. This value is typically set to 38400 or 76800
but can be 9600, 19200, 38400 or 76800.
Max master address
The max master is the MAC address of the highest master device on the BACnet MS/TP network
segment. Setting this number above the highest MAC address will decrease network performance.
For additional information, see the Corrigo PICS document, available via www.regincontrols.com
.
17.30 Other parameters
17.30.1 Start and stop delays for the fans
Use start delay if you wish one of the fans to start before the other and for example if you wish to
give the close-off dampers time to open before starting the fans. Use stop delay e.g. to create a cool-
down period when using electric heating. In order to avoid letting in too cold air, e.g. in the winter,
the heat exchanger will continue to run during the stop delay.
Delay SAF
Start: 60 s
Stop: 30 s
Delay EAF
Start: 0 s
Stop: 30 s
17.30.2 Retardation time
When switching two-speed fans from 1/1-speed to 1/2-speed there is a settable retardation time. The
same time applies to both fans.
Retardation time
1/1-1/2-speed
10 s
17.30.3 Heating at start-up and high speed blocking
At outdoor temperatures below the set value, the heating output will be forced to 100% before start-
up.
Two speed fans and pressure controlled fans can be blocked from using high speed at outdoor
temperatures lower than the set value. This function should not be combined with the function
”Outdoor compensation of pressure setpoint”. See the section Demand control.
Both functions need an outdoor temperature sensor.
Outd temp for
heat start: 3.0°C
Blocking of
1/1-speed: -10°C