CORRIGO VENTILATION 3.6 MANU

Table Of Contents
Manual Corrigo Ventilation, revision V Chapter 17 Configuration 107
TCP/IP
DHCP: Yes
Set static IP
Current IP
-
IP
192.168.001.234
Subnet mask
255.255.255.000
Current subnet mask
-
Current gateway
-
Default gateway
192.168.001.001
DNS
192.168.001.001
Current DNS
-
17.29.5 BACnet MS/TP Configuration
Upon delivery, the BACnet MS/TP protocol is disabled as a default. To enable BACnet
communication, the function must first be activated. The default communication settings upon
delivery are as follows:
Speed = 9600 bps
MAC address = 0
Device ID = 2640
Max Master = 127
Function port1
Slave
BACnet MS/TP
communication
port1
Active
Device name
CorrigoVentilation
MAC
0
Device ID low
2640
Device ID high
0 (x10000)
Speed
9600 bps
Max master address
127
Device name
This is the name of the device, as shown on the BAS when discovering devices.
MAC
The MAC address of the device. This needs to be unique only to the subnet to which the device is
attached.