CORRIGO VENTILATION 3.6 MANU
Table Of Contents
102 Chapter 17 Configuration Manual Corrigo Ventilation, revision V
Alarm text Prio Description
62
Sensor error extra unit temp
B
Malfunction in connected sensor
63 Sensor error external control
SAF
B Malfunction in connected sensor
64 Sensor error external control
EAF
B Malfunction in connected sensor
65 Sensor error SAF pressure 2 B Malfunction in connected sensor
66 Sensor error outdoor humidity B Malfunction in connected sensor
67 Sensor error intake temp B Malfunction in connected sensor
68
Sensor error extra sensor 2
B
Malfunction in connected sensor
69
Sensor error extra sensor 3
B
Malfunction in connected sensor
70
Sensor error extra sensor 4
B
Malfunction in connected sensor
71
Sensor error extra sensor 5
B
Malfunction in connected sensor
72 Sensor error extra SAF
pressure
B Malfunction in connected sensor
73 Sensor error extra EAF
pressure
B Malfunction in connected sensor
74
Sensor error backup 8
B
Malfunction in connected sensor
75
Sensor error backup 9
B
Malfunction in connected sensor
76
Sensor error backup 10
B
Malfunction in connected sensor
77 Alarm frequency converter
SAF
A Malfunction of frequency converter SAF
78 Alarm frequency converter
EAF
A Malfunction of frequency converter EAF
79 Communication error
frequency SAF
C Communication error Vacon NXL/Lenze
SMV/Omron V1000/Emerson
80 Alarm frequency converter
EAF
C Communication error Vacon NXL/Lenze
SMV/Omron V1000/Emerson
81 Communication error
expansion unit 1
C Communication problem with connected
expansion unit
82 Communication error
expansion unit 2
C Communication problem with connected
expansion unit
83 Warning frequency converter
SAF
C Alarm from frequency converter via
Modbus communication
84 Warning frequency converter
EAF
C Alarm from frequency converter via
Modbus communication
85 Output in manual mode C Analogue or digital output in manual mode
86 Time for service C Time for service
87 Y4 extra sequence control
manual
C Y4-Extra sequence in manual control
88 Restart blocked after power-
on
B Restart blocked due to earlier power
failure
89 Y5 extra sequence control
manual
C Y5 Extra sequence in manual control
90 Filter guard 2 B Filter guard pressure switch or analogue
filter switch activated. The analogue filter
switch may be flow dependent.
91
High temp extra sensor 1
-
High temperature extra sensor 1
92
Low temp extra sensor 1
-
Low temperature extra sensor 1