CORRIGO VENTILATION 3.6 MANU
Table Of Contents
Manual Corrigo Ventilation, revision V Chapter 17 Configuration 101
Alarm text Prio Description
27 Sensor error outdoor temp B Malfunction in connected sensor
28 Analogue deicing - Exchanger deicing activated by deicing
sensor
29 Rotation sentinel exchanger B Exchanger rotation sentinel alarm
activated
30
Malfunction fire damper
B
Fire damper exercise test failed
31 Supply air fan control error - Supply air pressure deviates too much
from the setpoint for too long.
32 Extract air fan control error - Extract air pressure deviates too much
from the setpoint for too long.
33 Supply air fan external
operation
C SAF run-signal received when unit is
stopped
34 Extract air fan external
operation
C EAF run-signal received when unit is
stopped
35 Ventilation manual mode C The unit is in manual mode
36 Manual supply air control C Supply air temp controller in manual
control
37 Manual supply air fan mode C Supply air fan in manual control
38 Manual supply air fan freq
control
C The SAF is in manual mode
39
Manual extract air fan mode
C
Extract air fan in manual control
40 Manual extract air fan freq
control
C The EAF is in manual mode
41
Manual heater control
C
The heater is in manual mode
42
Manual exchanger control
C
Heat exchanger output in manual control
43
Manual cooler control
C
Cooling output in manual control
44 Manual P1 heater C Heating circulation pump in manual
control
45 Manual P1 exchanger C Exchanger circulation pump in manual
control
46 Manual P1 cooler C Cooling circulation pump in manual
control
47 Manual fire damper C Fire dampers in manual control
48 Internal battery error A Internal battery needs replacing
49 Sensor error supply air temp B Malfunction in connected sensor
50
Sensor error extract air temp
B
Malfunction in connected sensor
51
Sensor error room temp 1
B
Malfunction in connected sensor
52
Sensor error room temp 2
B
Malfunction in connected sensor
53
Sensor error exhaust air temp
B
Malfunction in connected sensor
54 Sensor error extra sensor 1 B Sensor error Extra sensor 1
55 Sensor error SAF pressure B Malfunction in connected sensor
56
Sensor error EAF pressure
B
Malfunction in connected sensor
57
Sensor error deicing temp
B
Malfunction in connected sensor
58 Sensor error frost protection
temp
B Malfunction in connected sensor
59 Sensor error CO2 B Malfunction in connected sensor
60
Sensor error humidity room
B
Malfunction in connected sensor
61
Sensor error humidity duct
B
Malfunction in connected sensor