CORRIGO VENTILATION 3.6 MANU

Table Of Contents
100 Chapter 17 Configuration Manual Corrigo Ventilation, revision V
Alarm text
The alarm text that should be shown in the display when there is an alarm can be changed using E
tool
©
. For more information, see the E tool
©
manual.
Alarm list
The alarm text and priority columns show the factory set values.
Alarm text Prio Description
1 Malfunction supply air fan B Malfunction supply air fan
2
Malfunction extract air fan
B
Malfunction extract air fan
3
Malfunction P1 heater
B
Malfunction pump, heating circuit
4
Malfunction P1 cooler
B
Malfunction pump, cooling circuit
5 Malfunction P1 exchanger B Malfunction pump, liquid connected
exchanger
6 Filter alarm 1 B Filter guard pressure switch or analogue
filter switch activated. The analogue filter
switch may be flow dependent.
7
Flow guard
B
Flow switch activated
8 External frost guard A External frost protection thermostat
activated
9 Deicing pressure guard - Exchanger deicing pressure switch
activated
10 Fire alarm A Fire alarm activated
11 External switch C "External switch" activated
12
External alarm
B
External alarm activated
13 Supply air control error B Supply air temp deviates too much from
the setpoint for too long.
14 Humidity control error - The room humidity deviates too much
from the setpoint.
15
High supply air temp
B
Supply air temp too high
16 Low supply air temp B Supply air temp too low
17 Supply air temp max limit - Maximum limiting of supply air temp
active
18 Supply air temp min limit - Minimum limiting of supply air temp
active
19 High room temp B Room temp too high during room temp
control
20 Low room temp B Room temp too low during room temp
control
21 High extract air temp B High extract air temp during extract air
control
22 Low extract air temp B Low extract air temp during extract air
control
23 Electric heating is overheated A Heater high temperature limit switch
activated
24 Frost risk B Frost protection function is overriding the
control of the heater output
25 Low frost guard temp A Frost protection temperature below frost
limit value
26 Low efficiency B Heat exchanger efficiency below limit
value