W E TAK E B U I L D I N G AU TO M AT I O N PER SO N A L LY M AN UA L CORRIGO © Copyright AB Regin, Sweden, 2016
DISCLAIMER The information in this manual has been carefully checked and is believed to be correct. Regin however, makes no warranties as regards the contents of this manual and users are requested to report errors, discrepancies or ambiguities to Regin, so that corrections may be made in future editions. The information in this document is subject to change without prior notification.
Table of contents CHAPTER 1 ABOUT THE MANUAL ................................................................................................ 6 More information ........................................................................................................................ 6 CHAPTER 2 ABOUT CORRIGO ...................................................................................................... 8 2.1 Application choice ............................................................................
13.6 Holidays ............................................................................................................................. 73 CHAPTER 14 MANUAL / AUTO .................................................................................................. 74 CHAPTER 15 SETTINGS .............................................................................................................. 77 15.1 Control temp...........................................................................................
APPENDIX FREQUENCY CONVERTERS AND EC CONTROLLERS FOR HEAT EXCHANGERS.............
Chapter 1 About the manual This manual covers all the models in the Corrigo series used with the ventilation application. This revision covers program revisions from 3.5. More information More information about Corrigo can be found in: • Corrigo ventilation user guide – A simplified manual • Manual E tool© – Manual on how to configure the controllers using the PC software E tool©, available in Swedish, English, German and French.
Manual Corrigo Ventilation, revision V Chapter 1 About the manual 7
Chapter 2 About Corrigo The Corrigo series comprises three model sizes: 8, 15 or 28 in-/outputs. In each third generation model Corrigo, all applications are loaded in a separate memory area. The models have article number E...-3 (where 3 stands for third generation). A new feature as of version 3.3 are models with three communication ports. The 3 port Corrigo models have article number E...33 (where the initial “3” stands for 3 ports). For more detailed information, see chapter 16.
Controller E283DW-3 Serial: 011310170148 EXOreal version. EXOreal C revision: 3.2-0-07 SVN Build: 1420 MAC address and IP address. MAC adress 00:30:97:00:87:78 IP: 10.0.0.197 Battery status and memory size. Backup battery: 3.13 V Flash total size: 8192 kB Memory status and voltage frequency. Flash mem. Free: 1168 kB Mains power freq: 50Hz Communication: Communication mode selection. Serial TCP/IP Serial: Enables selection of EXOline address, communication speed, port mode and routing span.
Routing (pipe) Min Max PLN: 0 255 ELA 0 255 TCP/IP: Enables EXOline address selection EXOline address PLA: 254 ELA: 30 Choice of DHCP (Yes/No). DHCP: Yes Set static IP Current IP: 10.0.0.197 Also enables manual IP address and subnet mask setting before initiating the Corrigo. IP: 192.168.001.234 Subnet mask: 255.255.255.000 Default gateway and DNS name are also available from under this menu. Default gateway: 192.168.001.001 DNS: 192.168.001.001 Current subnet mask, gateway and DNS name.
Time/Date: Permits setting the time and date. Time: 11:50 Date: 2014-06-25 Weekday: Wednesday Input/Output: Enables input/output reading and writing. Analog Inputs Digital Inputs Universal Inputs Analog Outputs Digital Outputs Analog Inputs AI1: AI2: AI3: AI4: 0.0 0.0 0.0 0.0 0-10 0-10 0-10 0-10 Volts Volts Volts Volts Digital Inputs DI1: DI2: DI3: DI4: DI5: DI6: DI7: DI8: Off Off Off Off Off Off Off Off Universal Inputs UAI1: UAI2: UAI3: UAI4: UDI1: UDI2: UDI3: UDI4: 0.0 0.0 0.0 0.
2.1.2 Ventilation application The temperature controller is based on a supply air PI-controller for heating control with a preprogrammed set of control modes. A number of different control functions as well as analogue and digital in- and output functions can be bound to this controller. Certain functions are necessary, while others can be considered optional. The choice of which functions are to be used is free, the only restriction is the physical number of inputs and outputs of the different models.
Demand controlled ventilation In buildings with strongly varying occupancy the fan speeds or mixing dampers can be controlled by the air quality measured by a CO2 sensor. Support control When using the control function room control or extract air temperature control, it is possible to utilise support-heating and/or support-cooling.
E283DW3 E283W3 E282DW-3 E282W3 E281DW3 E281W3 E281D3 E2813 E152DW-3 E152W-3 E151DW3 E151D3 E151W3 E1513 E813 E81D3 Corrigo hardware overview AI* 2 2 4 4 4 4 4 4 4 4 4 4 4 4 4 4 DI* 3 3 4 4 4 4 4 4 8 8 8 8 8 8 8 8 UI* - - 4 4 4 4 4 4 4 4 AO* 1 1 3 3 3 3 3 3 5 5 5 5 5 5 5 5 DO* 2 2 4 4 4 4 4 4 7 7 7 7 7 7 7 7 RS485 • • • • • • • • • • • • BACnet/IP • • • • • • • •
2.2 Technical data Protection class .................................................................................................................. IP20 Display........................................................ 4 rows of 20 characters. Background illumination. LEDs Yellow ....................................................................................................... Settable parameter Red........................................................................................................
Inputs Analogue inputs AI.............................................. Settable 0…10 V DC or PT1000, 12 bit A/D Digital inputs DI .......................................................................................Potential-free closure Universal inputs UI...........................................Can be set to act as either an analogue input or a digital input with specifications as above Outputs Analogue outputs AO ...............................................
Chapter 3 Installation and wiring 3.1 Installation Corrigo can be mounted in a DIN-standard casing (minimum 9 modules), on a DIN-rail in a cabinet or, using a suitable front-mounting kit, in a cabinet door or other control panel. Ambient temperature: 0…50°C. Humidity: Max. 90 % RH, non-condensing. The picture below shows a wiring example for Corrigo E283W-3. 3.2.
3.2.2 Inputs and outputs The list of input and output functions in section 3.2.3 is a handy instrument to help you keep track of which inputs and outputs you will need to configure. Analogue inputs Analogue inputs must refer to an Agnd terminal placed in the same terminal block as the input being wired. Analogue inputs can, depending on the configuration, be used for either PT1000 temperature sensors or for 0…10 V DC analogue input signals, for example from a pressure transmitter.
24 V AC supply and 24 V AC relays L 2424VAC V AC N G G0 10 11 12 24 V DC supply and 24 V DC relays 24 V DC + - + - + - + - G G0 10 11 12 24 V DC 24 V AC supply and 24 V DC relays + - L V AC 2424VAC N + - + - + - Manual Corrigo Ventilation, revision V G G0 10 11 12 Chapter 3 Installation and wiring 19
24 V24 AC VAC 24 V DC supply and 24 V AC relays L N 24 V DC + - G G0 10 11 12 3.2.3 Input and output lists The lists below are intended to be used during commissioning to help you keep track of the desired input and output functions. The left column contains a description of the in-/output signal, the middle column displays the name of the corresponding signal in E tool© and the right column shows the text displayed in the Corrigo controller.
Description E tool© Display Intake temperature Intake temp Intake temp Extra temperature sensor 1 Extra sensor temp 1 Extsensor1 Extra temperature sensor 2 Extra sensor temp 2 Extsensor2 Extra temperature sensor 3 Extra sensor temp 3 Extsensor3 Extra temperature sensor 4 Extra sensor temp 4 Extsensor4 Extra temperature sensor 5 Extra sensor temp 5 Extsensor5 Extra pressure transmitter supply air Extra SAF pressure Extra SAF pressure Extra pressure transmitter extract air Extra EA
Description E tool© Display Extra alarm 2 Extra alarm 2 Ext alarm2 Extra alarm 3 Extra alarm 3 Ext alarm3 Extra alarm 4 Extra alarm 4 Ext alarm4 Extra alarm 5 Extra alarm 5 Ext alarm5 Extra alarm 6 Extra alarm 6 Ext alarm6 Extra alarm 7 Extra alarm 7 Ext alarm7 Extra alarm 8 Extra alarm 8 Ext alarm8 Extra alarm 9 Extra alarm 9 Ext alarm9 Extra alarm 10 Extra alarm 10 Ext alarm10 Start extra motor 1 Motor control 1 Motor1 Start extra motor 2 Motor control 2 Motor2 Run-i
Digital output signals Description E tool© Display Inactive output Not used Not used Start/stop Supply air fan Normal SAF start 1/1 normal speed SAF 1/1-speed Start/stop Extract air fan Normal EAF start 1/1 normal speed EAF 1/1-speed Start/stop Supply air fan Reduced SAF start 1/2 reduced speed SAF 1/2-speed Start/stop Extract air fan Reduced EAF start 1/2 reduced speed EAF 1/2-speed Start/stop circulation pump, heating Heating pump start P1 heating Fire damper Fire damper Fire da
24 Description E tool© Display Heating/cooling step 2 Heat/cool step 2 HeatCoolStep2 Heating/cooling step 3 Heat/cool step 3 HeatCoolStep3 Free cooling operation Free cool run Free cool run Pretreatment Pretreatment Pretreatment Split sequence active Split sequence Split sequence Run indication Run indication Run ind Pulse modulated heating output Heating PWM Heating PWM Activate Y4 Y4 extra sequence activate Y4 extra seq Activate Y5 Y5 extra sequence activate Y5 extra seq
Chapter 4 Commissioning General Before the Corrigo can be used, all inputs and outputs must first be configured, as well as all relevant parameters. All commissioning can be done using the Corrigo front panel display and buttons or using the external display unit E3-DSP. E tool© The best way however, is to configure the Corrigo by using E tool©. E tool© is a PC-based configuration program specially developed to simplify the commissioning of the Corrigo series.
Option 2: Read this manual in the order given below: The manual has been designed to act as a guide through the commissioning. The last chapters of the manual, not listed below, cover menus and functions that are not used during commissioning. Functional description Start by reading chapter 5. Functional description below. Some functions are essential to the working of the unit and must be included. Others are more of the nature of optional extras which can be excluded.
Manual/Auto Chapter 14. Learn to use manual control. A very useful tool for testing out and troubleshooting your system. Other functions Chapter 18. Alarm handling etc.
Chapter 5 Functional description 5.1 Temperature control General Corrigo has a choice of the following control modes: 1. Supply air control 2. Outdoor temperature compensated supply air control 3. Cascaded room temperature control 4. Cascade connected extract air temperature control 5. Outdoor temperature dependent switching between supply air control with outdoor temperature compensation and room temperature control 6.
Example: 0 % Cooling at HCOut = 30 % 100 % Cooling at HCOut = 0 % 0 % heat exch. at HCOut = 32 % 100 % heat exch. at HCOut = 50 % 0 % Heating at HCOut = 54 % 100 % Heating at HCOut = 100 % Output signal 100% 0% Controller signal 100% Cooling Heat exch. Heating 54% 50% 32% 30% 0% Heat demand In addition to these three, it is possible to connect two additional analogue output signals for control of optional sequences, Y4 extra sequence and Y5 extra sequence.
5.1.1 Control modes 1. Supply air control The supply air temperature is kept at the setpoint value by controlling the output signals for "Heating Y1", "Exchanger Y2", "Cooling Y3", "Extra sequence Y4" and “Extra sequence Y5”. A single PI control loop is used. A neutral zone can be set around the setpoint value. Example: If the setpoint is 18 °C and the neutral zone is 2 K, the cooling setpoint will be 19 °C and the heating setpoint will be 17 °C (FS=0 K).
6. Outdoor temperature dependent switching between supply air temperature control and extract air temperature control When the outdoor temperature is lower than a settable limit (winter), outdoor compensated supply air temperature control will be active, otherwise (summer) cascaded room temperature control as in control mode 4. 7. Outdoor compensated room temperature control The room temperature can be compensated when the outdoor temperature increases.
Frost protection The heater return water temperature is measured using the analogue input ”Frost prot.temp”. Low temperatures will generate an internal, proportional signal that is used to force the heating valve open thereby preventing freeze-up of the heater. The internal signal (“Internal signal”) will begin to rise as the frost protection temperature falls below “Alarm level” + “Prop. Band” in order to reach 100 % output when the signal has fallen to “Alarm level”.
Wiring suggestion high temp limit when using electric heating. Contactors are drawn inactivated. Note: It is important that the high temperature thermostat is hardwired to disconnect the power to the heater to ensure that the heating is shut down when the thermostat is activated even if the Corrigo should be faulty. 5.1.2.3 Water heating and electric heating The water heating is controlled by "Y1 heating", and the electric heating is controlled by the sequence "Split".
Deicing Deicing is activated either when the digital signal ”Deicing” is activated or when the value of the analogue input ”Deicing temp” falls below the de-icing limit (-3°C), or when the analogue signal ”Deicing pressure guard” rises above the set value for the current pressure. It is deactivated when the digital signal is reset, or alternatively when the analogue signal exceeds/falls below the limit value plus a settable differential.
Function to prevent the heat exchanger from freezing: A temperature sensor, exhaust air, outdoor air or extra controller sensor can be used as a prevention sensor. It is possible to set a starting temperature. This represents both the minimum time that the function should be active, the supply air fan (SAF) and extract air fan (EAF) compensation, as well as the minimum time before the next prevention cycle should begin. While the cycle is active, ”Deicing” is shown in the display and in E tool©.
5.1.4 Types of chillers Step controller Heating / DX cooling As alternative or complement to the above mentioned analogue control, heating and cooling can be activated in steps. The internal signal is then used to activate digital outputs for control of the heaters/chillers. Up to four heater outputs and three cooler outputs can be configured. There are two possible modes: Sequential control Each output step has individually settable on and off values in percent of the control signal.
DX cooling with exchanger control When running cascade control, the supply air controller setpoint is normally controlled by the room/extract air controller output signal. When DX cooling is activated, the supply air controller setpoint is lowered to five degrees (adjustable) below the setpoint given by the room/extract air controller. This prevents the DX cooling from being activated/deactivated too often.
Override of reduced speed for DX cooling Override to normal quantity of air for DX cooling when the unit runs on reduced quantity of air. The fans can be set to normal operation when cooling is required at high outdoor temperatures (e.g. >14°C, the same temperature limit as for blocking of DX cooling). 5.1.5 Support control Support control is normally used when room temperature control or extract air control has been configured. When extract air control is configured a room sensor must be installed.
If the outdoor sensor is located in the fresh air inlet duct and/or an extract air sensor is selected and ALL the start conditions are fulfilled, free cooling is activated and will run for 3 minutes to ensure that the temperature measurement when using an extract air sensor reflects the corresponding room temperature and that the outdoor temperature sensor senses the outdoor temperature even if it is placed in the fresh air inlet duct.
5.1.8 Enthalpy control Calculating the enthalpy means to calculate the energy content of the air, taking into consideration both the temperature and the air humidity. The value is given in energy per kilogram air (kJ/kg). If enthalpy control is configured, the enthalpy is calculated both indoors and outdoors. If enthalpy control is configured, enthalpy is calculated both outdoors and for the extract air.
5.1.11 Recirculation Recirculation is a function for distributing the air in the room using the supply air fan. The function can be used even when there is no heating or cooling demand. When using recirculation control, the extract air fan stops (but can also be set to run) and a recirculation damper opens which allows the air to circulate through the unit. Recirculation is activated either via a digital input signal or by connecting it to "Timer output 5".
5.1.13 Extra temperature sensor The input signals ”Extra Sensor Temp 1”, ”Extra Sensor Temp 2”, ”...”, ”Extra Sensor Temp 5”, can be used to add extra temperature sensors for supervision of temperatures that are not related to any control functions. Each sensor has three alarms tied to it: High temperature, Low temperature and Sensor error. “Extra temperature sensor 1” should be used for external setpoint input. “Extra Sensor Temp 1” should be used for external setpoint input. 5.1.
If the maximum limitation is 80 % RH and the hysteresis is 20 % RH, the controller output signal will begin decreasing at 60 % RH. When halfway to 80 % RH (i.e. when at 70 % RH), half the output signal will be damped. If the humidity in the duct still reaches 80 % RH, the entire output signal will be damped. Dehumidification An analogue output is used to control a dehumidifier. The output will increase on increasing humidity. A digital output can also be used to start a dehumidifier.
This compensation can be made depending on supply air, extract air, room or outdoor temperature. It is possible to compensate either one or both of the fans at the same time. It is possible to set which fan should then be compensated, the supply or extract air fan. Crosswise interlock Crosswise interlock of fans can be configured, which e.g. means that if one fan stops, the other fan will also stop.
Extra compensation curve As a complement to the above outdoor compensation, there is a function called ”Extra compensation curve pressure/flow setpoint” which can be used to set a compensation based on the room, extract air, supply air or outdoor temperature. The curve has three parameter pairs which correspond to the value of the compensation at three different temperatures.
The compensation can be selected to apply to both normal and reduced speed, or for normal speed only (factory setting = both speeds). Extra compensation curve As a complement to the above outdoor compensation, there is a function called ”Extra compensation curve” which can be used to set a compensation based on the room, extract air, supply air or outdoor temperature. The curve has three parameter pairs which correspond to the value of the compensation at three different temperatures.
Frequency control EAF with SAF slave The rotational speed of the extract air fan is controlled by a pressure transmitter which is placed in the extract air duct. The supply air fan has no pressure transmitter. Instead, the supply air fan output is made to follow the extract air fan control signal. A scaling factor can be added if the supply air fan characteristics are not the same as the characteristics of the extract air fan (only pressure control of the extract air fan is possible using this function).
Minimum limit For frequency controlled fans an adjustable minimum limit can be set individually on the supply air and extract air fan control signals.
When used with 2-speed fans they will start using reduced speed when the CO2 value rises above control value one and switch to normal speed when the CO2 value reaches control value two. The fans will stop when the CO2 value falls 160 ppm below control value one. If demand controlled ventilation is activated in combination with mixing dampers, and the CO2-value rises above the setpoint value, the dampers will let in more outdoor air. The function is controlled by a PI-controller. See section 5.1.
5.4.3 Extra control for external motor External control of an external (fan) motor can be configured. The fan is started via either a digital input or a time channel. A digital output activates the (fan) motor. A digital input is available for run time indication/motor protection. Inputs and outputs Motor control 1 DI DI Motor control 1 indication DI Motor control 2 DI Motor control 2 indication DO Motor control 1 start DO Motor control 2 start 5.
In- and outputs Heating Exch. Cooling Outdoor temperature sensor AI DO DO DO Start/stop circulation pump DI DI DI Run ind/alarm, circ. pump 5.6 Damper control 5.6.1 Close-off dampers The outdoor air and exhaust air ducts close-off dampers can be controlled by digital outputs or be hard-wired to the supply air fan relays for normal and reduced speed in such a fashion that the damper is open when the supply air fan is running.
DO Outdoor air damper DO Exhaust air damper DO Fire damper DI Fire alarm DI Fire damper end switch monitoring 5.7 Extended running and External switch The digital inputs for extended running can be used to force the unit to start although the timer says the running mode should be “Off”. Normal running always takes precedence over reduced speed. "Extended Operation, Normal" takes precedence over the timer output for reduced speed.
Stop function Each alarm offers the possibility to choose whether an activated alarm should stop the controller or not. The controller can also be set to run at reduced speed during alarms. The latter option can only be configured using E tool©. Automatic restart will take place when the alarm has been acknowledged. For some alarm types such as electric heating high temperature limit and water heating frost protection it would be dangerous to not stop the unit on alarm.
Chapter 6 Starting and stopping the unit 6.1 Start conditions The unit will be started and will run when any one of the following conditions is met: 1. Timer output for normal speed or timer output for reduced speed is ON 2. The unit is started manually using the Corrigo front panel or via E3-DSP 3. Digital input for extended running is activated 4. Support control is activated and the present room temperature is higher/lower than the preset starting value (Support heating/cooling) 5.
6.3 Start sequence Start of the unit will run according to the following sequence: 1. If the controller is configured for water heating and has an outdoor temperature sensor and the outdoor temperature is below +3ºC the heating valve is opened and the heating circulation pump is started. 2. If the controller is configured with a heat exchanger and has an outdoor temperature sensor and the outdoor temperature is below +15ºC the heat exchanger will be run at 100% capacity for a pre-set time. 3.
Chapter 7 Display, LEDs and buttons This section is applicable to Corrigo units with display and buttons but also to the hand terminal E3DSP which can be connected to Corrigo units without display and buttons. Room units are available with or without display, or as a touch display (see instructions and product sheets for ED-RU..., ED-RU-D... and ED-TCV). 7.1 Display The display has four rows of 20 characters and is backlit.
Regulator vent. sys 2008-11-20 13:30 System: Running Sp: 18.0 Act: 18.2°C Pressing DOWN will move you through the menu choices at this, the lowest level. UP will move you back through the choices. Which menus are shown depends on which access level you are using (see chapter eight for more information about logging on to higher levels).
Chapter 8 Access rights Running mode Temperature Time settings Access rights There are four different access levels. The Admin level has the highest access, while the Service, Operator and basic “no-log on” level have the lowest. The choice of access level determines which menus are shown, as well as which parameters can be changed in the displayed menus. Admin level gives full read/write access to all settings and parameters in all menus.
8.3 Change password As default Corrigo comes with the following passwords for the different levels: Admin Service Operator Normal 1111 2222 3333 5555 You can only change the password for log on levels lower or equal to the presently active level, i.e. if you are logged in as Admin you can change all passwords, but as Operator you can only change the Operator and Normal passwords. There is no point in changing the Basic password since access to that level is granted automatically to all users.
Chapter 9 Running mode Running mode Temperature Time settings Access rights Collected here are a number of menus showing running mode, selected functions, alarm events and status of inputs and outputs. Running mode Selected functions Alarm events Input/Output 9.1 Running mode, unit The unit’s running mode can be changed without logging on. Running mode Auto Running time SAF: 14.6 Running time EAF: 14.6 h h 9.2 Selected functions Shows the present configuration. These are read-only menus.
Fire damper funct Not active Operation when alarm Stopped Frost protection Active Cooling recovery No External setpoint Not active 9.3 Alarm events Alarm log which contains the 40 latest alarm events. The most recent event is listed first. The alarm log can only be used for viewing the alarm history. Alarms are handled in a special area, see section 18.1. 24 Nov 14:32 Malf. SAF B Acknowledged 9.
Chapter 10 Temperature Running mode Temperature Time settings Access rights Here you can view all actual and setpoint values for temperature control. The menu is visible to all users, regardless of log on level. However, to make changes you need at least Operator authority. The below menus are available, providing the corresponding input has been activated. Setpoints are available with a separate value for reduced speed. This is achieved using a temperature offset when the unit runs in reduced speed.
Outdoor comp setp 10.0°C = 18.0°C 15.0°C = 18.0°C In-between-values are calculated using straight lines between breakpoints. Setpoints for temperatures lower than the lowest breakpoint and higher than the highest breakpoint are calculated by extending the line between the two last breakpoints at either end. Example: At the lower end the setpoint is increasing by 1°C for every 5 °C lowering of the outdoor temperature. So the setpoint at –23°C would be 25°C + .6x 1.0°C = 25.6°C. Setpoint.
Control mode 7: Outdoor temperature compensated room control. Room temp1 Actual: 22.0°C Setp: 21.5°C Outdoor -20.0°C -15.0°C -10.0°C comp setp = 25.0°C = 24.0°C = 23.0°C Outdoor -5.0°C 0.0°C 5.0°C comp setp = 23.0°C = 22.0°C = 20.0°C Outdoor comp setp 10.0°C = 18.0°C 15.0°C = 18.0°C If cascade control max/min supply setp Max: 30.0°C Min: 12.0°C In control mode seven, the room setpoint is compensated based on outdoor temperature. Note that the curve must be reset for optimum functionality.
In control mode 8, the extract air setpoint is compensated based on outdoor temperature. Note that the curve must be adjusted for optimal functionality. Both the outdoor and extract air temperature are changeable for the curve. Support control heating Support heating Room temp for Start: 15.0°C Stop: 21.0°C Support control cooling Support cooling Room temp for Start: 30.0°C Stop: 28.0°C Frost protection temperature Frost protection Actual: 30.9°C Deicing exchanger Deicing exchanger Actual: 11.
Outd temp Act: 12.8 °C Humidity outdoors Act: 98.7% RH Indoor temp Act: 17.2 °C Humidity indoors Act: 55.
Chapter 11 Air control Pressure control SAF and EAF Pressure control can be entered in pascal (Pa) or inch water gauge (in.wg.). A factor (x100) is used in both the program and display when the unit “in.wg.” has been selected. When using pressure or flow controlled fans, the setpoint can be temperature compensated. The compensation has the default value 0 Pa, i.e. no compensation is added. The compensation is linear between the setting points. The compensation can be positive or negative.
Controller output compensation Not active Submenu “Compensation only when” Compensation only when 1/1-speed: No defrosting: No Flow units can be measured in both m3/h (cubic meters per hour) and in CFM (cubic feet per minute). Flow control SAF (there are corresponding menus for EAF) Flow control SAF Actual: 1800 m3/h Setp: 2000 m3/h Submenu "Setpoint" Flow control SAF Setp 1/1: 2000 m3/h Setp 1/2: 1000 m3/h Submenu "Outdoor compensation" Outdoor comp setp -20 °C = 0.0 m3/h 10 °C = 0.
Flow units can be measured in both m3/h (cubic meters per hour) and in CFM (cubic feet per minute). Manual frequency control SAF (there are corresponding menus for EAF) Frequency control manual SAF Output: 75% Submenu "Setpoint" Frequency control manual SAF Output 1/1: 75% Output 1/2: 50% Submenu "Outdoor compensation" Outdoor comp. outp.
Chapter 12 Humidity control Humidity control can be configured as Humidification, Dehumidification or both Humidification and Dehumidification. Two humidity sensors can be connected, a room sensor for control and an optional duct sensor for maximum limiting. The limit sensor can be omitted. The humidity control is handled by a PI-controller. The humidity sensors must give 0…10 V DC for 0…100 % RH. Humidity sensor room Humidity room Actual: 51.9% RH Setp: 50.
Chapter 13 Time settings Running mode Temperature Time settings Access rights General Corrigo has a year-base clock function. This means that a week-schedule with holiday periods for a full year can be set. The clock has an automatic summertime/wintertime change-over. Individual schedules for each week-day plus a separate holiday setting. Up to 24 individual holiday periods can be configured. A holiday period can be anything from one day up to 365 days.
If you want to run the unit from one day to another, e.g. from Mon 22:00 to Tue 09:00, the desired running time for both days must be entered. Normal speed Monday Per 1: 07:00 – 16:00 Per 2: 22:00 - 24:00 Normal speed Tuesday Per 1: 00:00 – 09:00 Per 2: 00:00 - 00:00 13.3 Timer Reduced speed These settings will be ignored if single speed fans are configured. Should periods for normal speed and periods for reduced speed overlap, normal speed takes precedence.
13.6 Holidays Up to 24 separate holiday periods for a full year can be set. A holiday period can be any number of consecutive days from 1…365. The dates are in the format: MM:DD. When the present date falls within a holiday period, the scheduler will use the settings for the weekday “Holiday”.
Chapter 14 Manual / Auto General In this menu the running mode of all the configured output signals and a number of control functions can be manually controlled. This is a very handy feature which simplifies the checking of individual functions in the Corrigo. The running mode for the whole unit is set in the menu "Running mode". See section 9.1. The supply air controller's output signal can be manually set (Manual/Auto) to any value between 0 and 100 %.
Y1 heating output Heating Auto Manual set: 0.0 Y2 heat exchanger Exchanger Auto Manual set: 0.0 Y3 cooling Cooling Auto Manual set: 0.0 Humidification/dehumidification Humidification/ Dehumidification Auto Manual set: 0% Circulation pumps: Heating, Exchanger and Cooling P1 heating Auto P1 exchanger Auto P1 cooling Auto Dampers: Outdoor air, Recirculation air, Exhaust air and Fire dampers Outdoor air damper Auto Exhaust air damper Auto Extra controller Extra ctrl unit Auto Manual set: 0.
Extra sequence Y4 Extra sequence Y4 Auto Manual set: 0.0 Extra sequence Y5 Extra sequence Y5 Auto Manual set: 0.
Chapter 15 Settings In this menu group all settings for all activated functions should be available. The menu group is only available when logging on as Admin. Depending on what choices have been made during configuration, some of the alternatives in this menu group may not be shown. Settings Control temp Control pressure Control flow Control humidity Control CO2 Control extra unit Alarm settings 15.1 Control temp Supply air controller Supply air control P-band: 33.0 °C I-time: 100.
Shutdown mode Shutdown mode P-band: 100.0 °C I-time: 100 s Frost protection control Frost protection Frost protection Active Setp shutdown: 25°C P-band active: 5°C Fast stop at frostprotection alarm Yes "Setp shutdown" is the shutdown mode setpoint. P-band active 5°C means that the frost protection controller will start overriding the heating output when the frost protection temperature is less than five degrees above the set frost alarm limit. The default alarm limit is 7°C.
15.3 Control flow Flow control SAF Flow control SAF P-band: 1000 m3/h I-time: 60 s Min.output: 0 % Flow control EAF Flow control EAF P-band: 1000 m3/h I-time: 60 s Min.output: 0 % 15.4 Humidity control Control humidity P-band: 100.0 %RH I-time: 300.0 s 15.5 Control CO2 Control CO2 P-band: 100.0 ppm I-tid: 100.0 s 15.6 Control extra unit Control extra unit P-band: 33.0 °C I-time: 100.0 s 15.7 Alarm settings Alarm settings Alarm limits Alarm delays Restore alarm 15.7.
Al lim room air High temp: 30.0 °C Low temp: 10.0 °C Alarm limit frost protection Alarm limit frost protection 7.0 °C Alarm limit, pressure Control dev SAF 40.0 Pa Control dev EAF 40.0 Pa Alarm limit Humidity Control deviation humidity: 10 % Alarm limit, exchanger efficiency Low efficiency 50.0 % Service alarm filter Service alarm (Filter alarm) Time until alarm activates: 0 month 15.7.
Alarm delay control dev pressure SAF: 30 min EAF: 30 min Alarm delay, Humidity Alarm delay control deviation humidity 30 min Alarm delay, exchanger efficiency Low efficiency 30 min Alarm delay, fan malfunction (SAF and EAF) Alarm delay malfunction SAF: 120 s EAF: 120 s Alarm delay, pump malfunction Alarm delay malfunc P1 heating: 5 s P1 cooling: 5 s P1 exchan: 20 s Alarm delay, misc. Filter guard1: 180 s Filter guard2: 180 s Flow switch: 5 s Frost prot: 0 s Ext. Frost prot.
15.8 Save and restore settings Restore factory settings: No Restore user settings: No In this menu, it is possible to restore all parameters to their factory settings or to the user settings they were saved as earlier, see below. Save user settings No The present configuration can be saved in a separate memory area and can later be restored using the previous menu, "Restore user settings".
Chapter 16 Expansion units 2 and 3 port Corrigo units are available with or without display. Both models have a TCP/IP port and one or two serial ports. For a list of the various models, see the Corrigo model overview in chapter 2. 16.1 Ports The ports are used for connecting to E tool© and, possibly, a SCADA system. In an E…3W-3 model, port 3 is the TCP/IP output. The serial ports (ports 1 and 2) are used for expansion purposes, e.
16.2.2 Expansion units EXOline Communication between the master and expansion units takes place via EXOline. The slave controllers will be given the addresses 241:1 and 241:2 (ELA:PLA) respectively. 16.2.3 Presigo pressure transmitter as an expansion unit Presigo is a pressure transmitter with one or two built-in differential pressure sensors. It is possible to connect up to four Presigos via EXOline.
Chapter 17 Configuration Start by logging on as Admin. See chapter 8. Move the marker using the DOWN and UP buttons until it is opposite the menu ”Configuration” and press RIGHT. The configuration main menu is shown (different menus are visible depending on the configured inputs and outputs).
17.1.1 Analogue inputs AI AI1: Sign: Outd temp Raw value: 18.4 Compensation:0.0 °C All analogue inputs are for PT1000 or 0…10 V. Input signals can be compensated e.g. for wiring resistance. The raw value will show the actual, uncompensated input value. If inputs have been assigned to pressure or flow control of fans, alternatively humidity or CO2 control, the following menus will appear: SAF Pressure at 0 V: 0.0 Pa 10 V:500.0 Pa Filter factor: 0.2 CO2 at 0 V: 0.0 ppm 10 V: 2000 ppm Filter factor: 0.
UAI1: Sign: SAF pressure Raw value:8.5 Compensation: 0.0 °C UDI1: NO/NC: NO Signal Not used Status: No To simplify adaptation to external functions, all universal inputs configured as digital inputs can be set to be either normally open, NO, or normally closed, NC. The inputs are as standard normally open, i. e. if the input is closed, the function connected to the input in Corrigo is activated.
2. Outdoor-temperature compensated supply air control. 3. Cascaded room temperature control 4. Cascade connected extract air temperature control. 5. Outdoor temperature dependent switching between outdoor compensated supply air temperature control and room temperature control 6. Outdoor-temperature controlled switching between Outdoor-temperature compensated supply air control and Cascade connected extract air temperature control. 7. Outdoor compensated room temperature control 8.
SAF with EAF slave / EAF with SAF slave If fan slave operation has been configured, there is a submenu for setting the CAV factor, a factor which determines the slave fan output in relation to the output of the controlling fan. SAF/EAF CAV factor 1.00 For more detailed description, see the section SAF with EAF slave under 5.4.1 Pressure control.
17.6 Extra sequence Y4 "Extra sequence Y4" can be configured to one of the following alternatives: "Active", "Active with cooling recovery", "Active with enthalpy control" and "Active with both cooling recovery and enthalpy control". Mode Extra sequence Y4 Not active 17.7 Extra sequence Y5 "Extra sequence Y5" can be configured to “Active” or “Not active”. Mode Extra Sequence Y5 Not active 17.8 Heating coil Heating Water The heater can be set to "Water", "Electric", "Water/Electric" or "Not used".
For detailed description of DX-cooling, se section 5.1.4 Step controllers. If DX cooling has been configured, there are submenus for setting of certain operation parameters. Min limit lowering If DX cooling is used in combination with room or extract air control, the supply air temperature minimum limit value can be lowered to give smoother (more continuous) running of the chillers. The set lowering of the limit value is activated when the DX cooling is running.
P1 Heating Pump stop: Yes Stop delay: 5 min Outd temp stop 10 °C Differential: 1.0 P1 Exchanger P1 exchanger Stop delay: 5 min P1 Cooling P1 cooling Stop delay: 5 min For a detailed description of pump functions, see the section Pump control. 17.12 Free cooling Free cool active:Yes Outd temp activation 22.0°C Outd temp night High: 18.0 °C Low: 10.0 °C Room temp min 18.
Support control active: Yes EAF running during support contr: Yes Minimum running time Min run time for support ctrl: 20 min For detailed description, see 5.1.5 Support control. 17.14 CO2 Demand control CO2/VOC active Never Type: Dampers Min. time: 20 min Activation 1/2-speed: 1/1-speed: diff: level 800 ppm 1000 ppm 160 ppm For detailed description, see the section Demand control. 17.15 Fire function Fire dampers are normally closed and configured to open if a fire takes place.
“Running time” is the time the damper actuator needs to open or close. “Hour for exercise” is the hour of the day at which you want the function to be run. For detailed description of damper exercising, see the section Damper control. It is possible to select whether the outdoor damper should remain open or closed during an eventual fire. For the damper to remain open during fires, the running mode must be set to a setting other than “Stopped”. Outdoor air damper when fire Always open 17.
Cooling recovery run when enthalpy is greater outd than indoors : Active For a detailed description, see section 5.1.8 Enthalpy control. 17.21 External setpoint An external setpoint device, for example TBI-PT1000 or TG-R4/PT1000 can be connected. The setpoint device must follow the PT1000 resistance curve. The setting range can be restricted. External setpoint Not active Min setp: 12.0°C Max setp: 30.0°C For details, see section 5.1.10 External setpoint. 17.
17.23 Actuator type Choose output signals to the actuators connected to the analogue control outputs: 0…10 V DC, 2…10 V DC, 10…0 V DC or 10…2 V DC.
Step controller Heating activation levels for sequential control. For binary control the activation levels are calculated by the controller depending on the number of steps involved Start Stop Start Stop step1: 10 step1: 5 step2: 45 step2: 40 % % % % Start Stop Start Stop step3: step3: step4: step4: % % % % 70 65 95 90 Control parameters. Heater groups is used to calculate activation levels for binary control. "Hyst." is the switching differential used for each step when running binary control.
17.25.3 Step controllers Change-over The digital output signals "Heating/cooling step 1", "Heating/cooling step 2" and "Heating/cooling step 3" are used for step controllers during Change-over control (see section 5.1.12). They have the same functions as other step controller outputs, but are set to either heating or cooling depending on whether heating or cooling is required.
If a sensor is configured in the intake duct (”intaketemp”) this temperature will be compared with the outdoor temperature. If the temperature in the intake duct does not exceed the outdoor temperature by more than 1°C (adjustable) 5 minutes (fixed) after start-up when using preheating, preheating will be aborted. The same conditions apply to precooling, i.e. if the intake temperature is not more than 1°C (adjustable) cooler than the outdoor temperature, precooling will be aborted.
Alarm text The alarm text that should be shown in the display when there is an alarm can be changed using E tool©. For more information, see the E tool© manual. Alarm list The alarm text and priority columns show the factory set values.
Alarm text Prio Description 27 Sensor error outdoor temp B Malfunction in connected sensor 28 Analogue deicing - Exchanger deicing activated by deicing sensor 29 Rotation sentinel exchanger B Exchanger rotation sentinel alarm activated 30 Malfunction fire damper B Fire damper exercise test failed 31 Supply air fan control error - Supply air pressure deviates too much from the setpoint for too long.
Alarm text Prio Description 62 Sensor error extra unit temp B Malfunction in connected sensor 63 Sensor error external control SAF B Malfunction in connected sensor 64 Sensor error external control EAF B Malfunction in connected sensor 65 Sensor error SAF pressure 2 B Malfunction in connected sensor 66 Sensor error outdoor humidity B Malfunction in connected sensor 67 Sensor error intake temp B Malfunction in connected sensor 68 Sensor error extra sensor 2 B Malfunction in c
Alarm text Prio Description 93 High temp extra sensor 2 - High temperature extra sensor 2 94 Low temp extra sensor 2 - Low temperature extra sensor 2 95 High temp extra sensor 3 - High temperature extra sensor 3 96 Low temp extra sensor 3 - Low temperature extra sensor 3 97 High temp extra sensor 4 - High temperature extra sensor 4 98 Low temp extra sensor 4 - Low temperature extra sensor 4 99 High temp extra sensor 5 - High temperature extra sensor 5 100 Low temp extra sensor
17.29 Communication 17.29.1 Modbus communication Corrigo can be connected to a network for Modbus communication. Modbus communication slave, port 1 Not Active If Modbus communication is activated, you can set the address etc. Modbus communication takes place using 1 stop bit. Modbus address: 1 Speed: 9600 bps Two stop bits:Yes Parity:No NOTE: Only one stop bit can be used. Slave For connection to E tool© and a Modbus SCADA system.
Modbus address: Supply air fan = 1, Extract air fan = 2, Parallel supply air fan = 3, Parallel extract air fan = 4 Speed: 9600 bps, 1 stop bit, no parity For additional settings for every model, see Appendix 1 at the end of this document. Type of freq conv connected on Modbus Vacon NXL Dual? No External display ED-TCV or ED/RU-RUD can be used as an external display.
17.29.4 BACnet/IP configuration Upon delivery, the BACnet/IP protocol is disabled as a default. To enable BACnet communication, simply change the setting “Not active” to “Active”. The protocol will now be available for use: TCP/IP BACnet/IP communication Active Device name CorrigoVentilation BBMD address Device ID low 2640 Device ID high 0 (x10000) Device name This is the devices name that is shown on the BAS when a device is discovered.
TCP/IP DHCP: Yes Set static IP Current IP - IP 192.168.001.234 Subnet mask 255.255.255.000 Current subnet mask Current gateway Default gateway 192.168.001.001 DNS 192.168.001.001 Current DNS - 17.29.5 BACnet MS/TP Configuration Upon delivery, the BACnet MS/TP protocol is disabled as a default. To enable BACnet communication, the function must first be activated.
Device ID The ID of a device, used to identify it on the BACnet network. This number cannot be duplicated anywhere on the BACnet network and must therefore be unique. To set an ID value of 34600, the low number would be set to 4600 and the high number to 3. Speed Sets the communication speed of the MS/TP network. This value is typically set to 38400 or 76800 but can be 9600, 19200, 38400 or 76800.
17.30.4 Start delay exchanger Start delay exch 0 s 17.30.5 Exchanger to 100% at start and alarm delay at start To minimise the risk of freeze-up problems, the heat exchanger can be forced to maximum capacity for the set time at start-up. To eliminate the risk of, for example, fan pressure alarms at start-up, all alarm functions can be suppressed for the set time.
Split settings extra sequence Y4 0% at HCOut= 0% 100% at HCOut= 0% Split settings extra sequence Y5 0% at HCOut= 0% 100% at HCOut= 0% Output signal 100% 0% Controller signal 100% Cooling Heat exch. Heating 54% 50% 32% 30% 0% Heat demand 17.30.7 Outdoor temp. for control mode change If the unit is configured for combined Supply air/Room control this menu permits the setting of the change-over outdoor temperature. Outdoor temp for control mode change 13.0°C 17.30.8 Split of optional temp.
Fast stop on alarm “Electric heating is overheated”: No 17.30.10 Automatic restart at power-up The function ”Automatic restart at power-up” makes it possible to block automatic restart of the unit at power-up. At power-up, the B-alarm ”Restart blocked after power on” is generated. Once this alarm has been acknowledged, the unit will start. Automatically restart after power-on: Yes 17.31 System 17.31.1 Change language Use this menu to change the display language.
2004-08-15 11:28 System: Running Sp:22.0°C Act:21.8°C Y1:0% Y2:93% Y3:0% Type 3 The first line shows the date and time. The second line shows the present running status. The third line shows the present temperature setpoint and actual values. The fourth line shows the present SAF and EAF pressures. 15/03/2004 11:28 System: Running Sp:22.0°C Act:21.8°C SF:1100Pa EF:1050Pa Type 4 The text on the first line can be changed using E tool©. The second line shows the date and time.
17.31.5 Display anywhere (remote control) If multiple Corrigo units are connected in a network, it is possible to remote control a unit in the network from a unit with display. You do this by entering the address of the unit you wish to remote control in the unit with display. The function is aborted by pressing the buttons UP, OK and DOWN simultaneously. Address for remote communication (PLA:ELA) : 00:00 17.31.
Chapter 18 Other functions 18.1 Alarm handling If an alarm condition occurs, the red Alarm LED on the front panel of units with display or the Alarm LED on a connected display unit will start flashing. The LED will continue to flash as long as there are unacknowledged alarms. Alarms are logged in the alarm list. The list shows type of alarm, date and time for the alarm and the alarm class (A, B or C alarm).
18.4 Language When the start menu is displayed, pressing the RIGHT button three times will display a menu in which the language can be changed. The different language files are stored in the application memory and are downloaded to the work memory. If a Corrigo via E tool© has been reloaded with a newer program revision than the factory revision, the controller will not allow language files to be downloaded from the application memory.
Remove the cover by pressing down the locking torques at the edge of the cover using a small screwdriver, and at the same time pulling the edges outwards. Battery location Grip the battery firmly with your fingers and lift it upwards until it rises from its holder. Press the new battery firmly down into place. Note: To preserve correct polarity, the battery can only be inserted the “right way round”! 18.7 Start-up wizard The start-up wizard is a function that can be activated in "Configuration"/"System".
Choose language English In the second menu, the setpoint is set. The appearance of the menu depends on which control type has been configured. Supply air temp Setp: 18°C In the third menu, time and date are set. Time: 14:27 Date: 2013-11-25 Weekday: Tuesday In the fourth menu, the running time for normal speed Monday – Friday is set. Normal Monday Per 1: Per 2: speed Friday 07:00 – 16:00 00:00 – 00:00 In the fifth menu, the running time for normal speed Saturday, Sunday and holiday is set.
18.8 Energy calculation The total energy consumption of the air handling unit can be obtained by internally calculating the various partial outputs of system components. By combining the various outputs of heaters/coolers, fans, etc., current power consumption is calculated based on their combined output. 18.
Index A Access rights, 57 Actuator type, 95 Address, 112 Air control, 66 Alarm Setting, 98 Alarm events, 60 Alarm list, 99 Alarm settings, 78 Alarms, 51 Alarm delay at startup, 108 Alarm delays, 79 Alarm handling, 113 Alarm limits, 78 Alarm list, 99 Analogue inputs, 17 Analogue outputs, 17 Automatic restart at power-up, 110 B Battery exchanger.
Extra sequence Y4, 89 Extra sequence Y5, 89 Extra temperature sensor, 41 F Fans Control, 42 Delays, 107 Frequency control EAF with flow control SAF, 46 Frequency control external control signal, 45 Frequency control flow, 44 Frequency control SAF with EAF slave, 46 Frequency control SAF with flow control EAF, 46 Interlock, 88 Manual frequency control, 45 Pressure control, 43 Retardation time, 107 Timer output ½ speed, 71 Timer output 1/1 speed, 70 Fire dampers, 50, 52, 92 Exercising, 50 Flow control Extra
Pressure control, 43 Extra compensation curve, 43 Outdoor compensation, 43 Setpoint, 43 Pretreatment, 98 Pump control, 49, 90 R Recirculation, 40, 97 Remote control, 112 Restore alarm, 80 Revision number, 113 Rotating exchanger, 33 Run indication / Motor protection, 94 Running mode, 59 Running mode, unit, 59 Running time, 3-position actuators, 95 S Save and restore settings, 81 Selected functions, 59 Setpoint fan control, 66 Setpoint humidity control, 69 Setpoint, external, 39, 94 Setpoints temperature, 6
Appendix
Appendix Frequency converters and EC controllers for heat exchangers Version 3.
Address Modbus register Name Scaling Type 2101 32101, 42101 FB status word - Binary The variables presented in the display of the Corrigo are: Frequency (Hz), Current (A), Output (kW), Accumulated power (kWh). Lenze No settings necessary. Lenze frequency converters are controlled via Modbus. Communication, alarms and certain indications can be read.
• H5-11 (0x43C): Communication Enter Function, default=1 (Enter command not necessary) • H5-12 (0x43D): Run command, default=0 (bit 0=forward start/stop, bit 1= reverse start/stop) • b1-01 (0x180): Frequency Reference selection 1, default = 2 (via Modbus) • b2-01 (0x181): Run command selection 1, default = 2 (via Modbus) Omron frequency converters are controlled via Modbus. Communication, alarms and certain indications can be read.
• Deactivate the unit. The display should read “iH 0.0”. This is performed by opening terminal B4. • Set parameter 10 to ”L3”, i.e. all parameters up to and including 95 can then be altered. • Set parameter 43 to 9.6 (9600 baud). Emerson frequency converters are controlled via Modbus.
LS iS7 The following signals can be read/written from/to the frequency converter: Address Modbus register Name Scaling Type 5 30005,40005 FB speed reference (SP) 10 % 6 30006,40006 FB status word - Binary 10 30010,40010 Motor frequency 100 Hz 791 30791,40791 Torque 100 % 786 30786,40786 RPM 1 Rpm 784 30784,40784 Motor current 10 A 790 30790,40790 Output 10 kW 789 30789,40789 Voltage 10 V 14 30014,40014 Status change - Binary 816 30816,40816 Alarm - Bina
Danfoss FC 101 Danfoss frequency converters are controlled via Modbus. Communication, alarms and certain indications can be read.
Eltwin A/S EC controller (for heat exchangers), RHC 200 Communication takes place using address 7, 9600 bps, 8 bits, no parity and 1 stop bit. Version 1.01, 2015-04-03 Address Modbus register Name Scaling Type 1 30001 Running mode - Bit 0 = Operation 0: Stop 1: Run Bit 3 = Reset 1: Reset 2 30002 Speed 1 0…100.