COMMISSIONING RECORD206951 (A008) FORM

Commissioning record |
3
Function Default settings Set value
Frost protection
(Only visible for units without EL
heater)
Mode (EL unit Off) On
On
˜
Off
˜
Frost limit temperature: See alarm settings/low frost guard temp See alarm settings/low frost guard temp
Set point when stopped (return
water):
C _____ ° C
P-band when running 5 _____
Free cooling
Mode:
Off On ˜ Off ˜
Activation at outdoor temp. higher
than:
22° C _____ ° C
Stopped at outdoor night temp.
higher than:
15° C _____ ° C
Stopped at outdoor night temp.
lower than:
C _____ ° C
Stopped at room temp. lower than: 18° C _____ ° C
Hour for start/stop: Start: 00:00 Stop: 07:00 Start: _____ Stop: _____
Time to block heat output after free
cooling:
60 min. _____ min.
Fan output when free cooling: SAF: 0% EAF: 0% SAF: _____ % EAF: _____ %
Cool recovery
(Not applied for SF units)
Mode: On
On
˜
Off
˜
Start at temp. difference: C _____ ° C
Fire function
Operation in case of fire alarm Stopped
Stopped
˜
Only EAF
˜
Only EAF
˜
Only SAF
˜
Only SAF
˜
Normal run
˜
Normal run
˜
Continuous run
˜
Continuous run
˜
Fire alarm input Normally open
Normally open
˜
Normally closed
˜
Normally closed
˜
Defrost function
(Not applied for SF, TR, SR, FR units)
Exchanger de-icing
(Only visible for units with cross/
counter flow exchanger)
Yes
Yes
˜
No
˜
By-pass active: On
On
˜
Off
˜
Stop deicing
On
On
˜
Off
˜
Activation temp
0,0
_____
Stop temp SAF
-8° C
_____° C
Setp Press dev
50 %
_____%
Stop hyst
60 %
_____%
206951 | A008