COMMISSIONING RECORD206951 (A008) FORM

Commissioning record |
7
Alarm settings Def. settings Set value Alarm settings Def.settings Set value
12. External alarm 43. Manual cooler control
Class: B _____ Class: C _____
Delay: 0 s _____ Delay: 0 s _____
Stop ventilation unit if alarm active: No _____ Stop ventilation unit if alarm active: No _____
Alarm text: External alarm Alarm text: Manual cooler
control
15. High supply air temp 44. Manual P1–heater
Class: B _____ Class: C _____
Delay: 30 min _____ Delay: 0 s _____
Stop ventilation unit if alarm active: No _____ Stop ventilation unit if alarm active: No _____
Alarm text: High supply air temp Alarm text: Manual P1–heater
High supply temp. 35° C
16. Low supply air temp 46. Manual P1–Cooler
Class: B _____ Class: C _____
Delay: 30 min _____ Delay: 0 s _____
Stop ventilation unit if alarm active: No _____ Stop ventilation unit if alarm active: No _____
Alarm text: Low supply air temp Alarm text: Manual P1–cooler
Low supply air temp.: 10° C _____
19. High room temp 48. Internal battery error
Class: B _____ Class: B _____
Delay: 30 min _____ Delay: 5 s _____
Stop ventilation unit if alarm active: No _____ Internal battery error: No _____
Alarm text: High room temp. Alarm text: Sensor error supply
air temp.
High room temp. 30° C _____
20. Low room temp. 49. Sensor error supply air temp.
Class: B _____ Class: B _____
Delay: 30 min _____ Delay: 5 s _____
Stop ventilation unit if alarm active: No _____ Stop ventilation unit if alarm active: No _____
Alarm text: Low room temp.
Alarm text: Sensor error supply
air temp.
Low room temp.: 10° C _____
21. High extract air temp. 50. Sensor error extract air temp
Class: B _____ Class: B _____
Delay: 30 min _____ Delay: 5 s _____
Stop ventilation unit if alarm active: No _____ Stop ventilation unit if alarm active: No _____
Alarm text: High extract temp.: Alarm text: Sensor error
extract air temp.:
High extract temp.: 30° C _____
206951 | A008