IMO EX E
133285 / 8118609300
2015-03-24·BA00·III·en·05
Technical data
7
Terminal Boxes
Series 8118/1, 8118/2
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
5.1 Operation
Maximum number of conductors depending on the conductor cross-section and the
number of terminals under load for temperature class
T6 with T
a
( 40 °C or T5 with T
a
( 55 °C:
8118/112, 8118/114
Rated operational cur-
rent
Max. number of conductors *
)
for conductor cross-section
1.5 mm
2
2.5 mm
2
4 mm
2
3 A 16 **
)
any any
6 A 16 **
)
12 **
)
any
10 A 16 **
)
12 **
)
12 **
)
16 A 6 **
)
12 **
)
12 **
)
20 A - 6 **
)
12 **
)
25 A - - 8 **
)
8118/122, 8118/124
Rated operational cur-
rent
Max. number of conductors *
)
for conductor
cross-section
1.5 mm
2
2.5 mm
2
4 mm
2
6 mm
2
3 A 26 **
)
any any any
6 A 26 **
)
26 **
)
any any
10 A 26 **
)
26 **
)
22 **
)
any
16 A 6 **
)
14 **
)
22 **
)
20 **
)
20 A - 6 **
)
22 **
)
20 **
)
25 A - - 8 **
)
20 **
)
35 A - - - 4 **
)
8118/132, 8118/134
Rated operational cur-
rent
Max. number of conductors *
)
for conductor cross-section
1.5 mm
2
2.5 mm
2
4 mm
2
6 mm
2
10 mm
2
3 A 36 **
)
any any any any
6 A 36 **
)
36 **
)
any any any
10 A 26 **
)
36 **
)
32 **
)
any any
16 A 6 **
)
18 **
)
32 **
)
24 **
)
any
20 A - 6 **
)
22 **
)
24 **
)
20 **
)
25 A - - 8 **
)
24 **
)
20 **
)
35 A - - - 6 **
)
20 **
)
50 A - - - - 4 **
)
*
)
Each inserted conductor and each internal connection conductor is considered as conductor.
Jumpers and earth leads are not considered as conductors.
**
)
When using these table values, the simultaneity factors or load factors may be
taken into account according to IEC 439. Mixed arrangements with circuits of
different cross sections and currents are possible by the shared use of the different table values.