DMV NEX

4
Systemair Sverige AB · Industrivägen 3 · 739 30 Skinnskatteberg · Phone +46 222 440 00
220-240V ~ 50Hz - Air performance measured according to ISO 5801 a 230V 50Hz, air density 1,2 kg/m
3
.
Product fiche - ErP Directive, Regulations 1253/2014 - 1254/2014
Note: Air flow and thermal efficiency of the NEX unit is measured based on pair. That is, not valid for only 1 unit.
a) Mark - Systemair
b) Model - DMV NEX 100
c) SEC class - A
c1) SEC warm climates kWh/m2.a -17
c2) SEC average climates kWh/m2.a -40,6
c3) SEC cold climates kWh/m2.a -81,8
Energy label - Yes
d) Unit typology - Residential - bidirectional
e) Type of drive - Multi-speed drive
f) Type of Heat Recovery System - Heat recovery
g) Thermal efficiency of heat recovery % 74
h) Maximum flow rate at 0 Pa m
3
/h 25
i) Electric power input at maximum flow rate W 3,5
j) Sound power level (L
WA
) dBA 39
k) Reference flow rate m
3
/h 18
l) Reference pressure difference Pa 10
m) Specific power input (SPI) W/m
3
/h 0,139
n1) Control factor - 0,65
n2) Control typology - Local demand control
o1) Maximum internal leakage rate % N/A
o2) Maximum external leakage rate % 1
p1) Internal mixing rate % N/A
p2) External mixing rate % N/A
q) Visual filter warning - Yellow led
r) Instructions to install regulated grilles - N/A
s) Internet address for pre/disassembly instructions - www.systemair.com
t) Airflow sensitivity to pressure variations % N/A
u) Indoor/outdoor air tightness m
3
/h 18
v1) AEC - Annual electricity consumption - warm
climates
kWh 1
v2) AEC - Annual electricity consumption - average
climates
kWh 1
v3) AEC - Annual electricity consumption - cold
climates
kWh 1
w1) AHS - Annual heating saved - warm climates kWh 19,5
w2) AHS - Annual heating saved - average climates kWh 43,1
w3) AHS - Annual heating saved - cold climates kWh 84,3
Air-flow at different speed m
3
/h 25/21/17/14/10
Power consumption at different speed W 3,5/3/2,5/2/2
Sound pressure at 3m at different speed
1
dB(A) 27/23/18/14/9
Thermal efficiency % 70/72/74/78/82
Ambient temperature max °C -20°C ÷ +50°C
Degree of protection IP - X4
Marking/Mark -
1 Sound pressure level at 3 m in free field, for comparative purposes only.
I II
2016 1254/2014
ENERGIA · ʫʻʫˀʧʰ˔ · ȵɁȵɆȳȵȻȰ · ENERGIJA · ENERGY · ENERGIE ͽEZ'/
A+
A
B
C
D
E
F
G
254519 DMV NEX 100
39
dB
25 m
3
/h