Topvex SoftCooler TR Installation instructions CE208767 A006
Table Of Contents
- 1 Declaration of Conformity
 - 2 Warnings
 - 3 Refrigerant Control/Reporting
 - 4 Product information
 - 5 Transport and storage
 - 6 Installation
 - 7 Function Description
 - 8 Commissioning protocol
 
18
| Commissioning protocol
Moment Done Note
Keep the compressor running.
Read the below values via the display of the frequency
converter, see section ”Frequency converter, quick guide”,
in Operating and Maintenance Instructions. First set the
parameter for reading, then let the door of the Topvex
SoftCooler be closed for at least 5 minutes before reading:
• Output frequency (Param d001)
• Output current (Param d002)
• Condenser pressure (Param d004)
Output frequency __________________Hz
Output current ____________________Hz
Condenser pressure ______________bar
Note:
Important! Restore the cooling operation to Auto:
• Log in to the control unit as Service (0612)
• Select menu Data & Settings > In-/Output
status > Heating/Cooling Sequences
• Set Mode for Cooling to Auto
Notes:
208767 | A006