Topvex SoftCooler TR Installation instructions CE208767 A006
Table Of Contents
- 1 Declaration of Conformity
 - 2 Warnings
 - 3 Refrigerant Control/Reporting
 - 4 Product information
 - 5 Transport and storage
 - 6 Installation
 - 7 Function Description
 - 8 Commissioning protocol
 
Commissioning protocol |
17
Moment Done Note
Select the menu Configuration > Functions >
Temperature control:
• Set Cooling recovery mode to On
Select the menu Configuration > I/O allocation
settings > Digital outputs:
• Set Signal for Step controller 1 step 1 to DO4
• Set Signal for Step controller 1 step 2 to DO5
Select the menu Configuration > I/O allocation
settings > Digital inputs:
• Set Signal for Extended operation normal speed
to Select I/O (or to any other free DI)
• Set Signal for Feedback cooling (SEQ-C) to DI4
Note:
Note: DI4 cannot be used for extended run
when Topvex SoftCooler is used.
Select the menu Data & Settings > Temperature
control > Cooling:
• Set Min switch time to 60 s
• Set Step 1 start point to 10%
• Set Step 1 stop point to 0%
• Set Step 2 start point to 10%
• Set Step 2 stop point to 5%
• Set Reduction of min limit supply air if
active DX-cooling to 0 °C
8.4 Before first compressor start
To avoid damage on the compressor the oil in the compressor crankcase must be heated before the first start.
Moment Done Note
Stop the Supply- and extract fan (via the Topvex air
handling units safety switch)
Turn on the mains supply for the Topvex SoftCooler via the
working switch, make sure that the voltage is on (the
display in the frequency converter lights up) Wait for
minimum 2 hours so that the oil will reach about +30° C!
8.5 Control cooling operation
Moment Done Note
Start the Supply- and extract fan (via the Topvex air
handling units safety switch). Run the unit on dimensioning
airflows.
Supply air ________________m
3
/h
Extract air _______________m
3
/h
Start the compressor by establishing a 100% cooling
demand:
• Log in with service level using password 0612
• Select menu Data & Settings > In-/Output
status > Heating/Cooling sequences
• Set Mode for Cooling to Manual
• Set Manual for Cooling to 100%
Run the compressor for at least 10 minutes.
Then read the Extract-, Outdoor- and Supply air
temperature via the display of the control unit (in the menu
Temperature).
Outdoor air temperature __________°C
Supply air temperature ___________°C
Extract air temperature __________°C
Let the compressor run.
Measure the hotgas- and liquid line temperature with a
strap-on temperature detector.
Hotgas temperature ___________°C
Liquid line temperature _________°C