14
| Cleaning
Activities cont'd
Clean the fan/ventilation system (see 12 Cleaning, page
14).
X X
Check the screwed connections for damages/defects and
check that they are firmly seated.
X
See normal operating
conditions
Check the fan intake is free from contamination.
X X
Check that the fan and its components are being used
correctly.
X
See normal operating
conditions
Check the current consumption and compare this with the
rated data.
X X
Check the vibration dampers (if used) are working
correctly and check for visible damage and corrosion.
X
See normal operating
conditions
Check the electrical and mechanical protective equipment
is working correctly.
X
See normal operating
conditions
Check the fan’s rating plate is legible.
X X
Check the connection clamps and screwed cable
connections for damage/defects, and check that they are
firmly seated.
X
See normal operating
conditions
Check the flexible connectors for damage.
X
See normal operating
conditions
Spare parts
♦ Use original spare parts from Systemair only.
♦ When ordering spare parts, please specify the serial number of the fan. This can be found on the name plate.
12 Cleaning
Safety information
♦ Observe 2 Important safety information, page 1
Procedure
Keeping the fan clean extends its service life.
• Install a filter monitor.
• Change the filters of the ventilation system.
• Do not use steel brushes or sharp-edged objects.
• Do not use a high-pressure cleaner (steam jet cleaner) under any circumstances.
• Do not bend the fan blades when cleaning.
• When cleaning the impeller, pay attention to balance weights that have been positioned
• Keep the airways of the fan clear and clean them if necessary with a brush.
13 Deinstallation/dismantling
Deinstall and dismantle the fan in reverse order of installation and electrical connection.
14 Disposal
♦ Ensure material is recycled. Observe national regulations.
♦ The device and the transport packaging are predominantly made from recyclable raw materials.
♦ Disassemble the fan into its components.
♦ Separate the parts according to:
• reusable material
• material groups to be disposed of (metal, plastics, electrical parts, etc.)
| 005