PRE HEATER INST TOPVEX SC TC 247019

How to set up the function |
5
4.3 Allocation
Configuration > I/O allocation settings
Select I/O (in-/output) placement for the connected temperature sensor and control/feedback signals to/from the elec-
tric heater in the Configuration > I/O allocation settings submenus.
Caution
Do not use the same in- or output for several functions.
Overview:
Configuration > I/O allocation settings >
Analog inputs
22 Sept 12:43
Analog inputs
Device Position
Intake air temperature
Controller AI4
Preheater temperature
PDT2 UI1
Configuration > I/O allocation settings >
Digital inputs
22 Sept 12:43
Digital inputs
Device Position
Feedback preheater
Controller DI6
Configuration > ... > Digital inputs> Feedback
preheater
22 Sept 12:43
Name
Feedback preheater
Original name Feedback preheater
Contact function
Normally closed
Configuration > I/O allocation settings >
Analog outputs
22 Sept 12:43
Analog outputs
Device Position
Preheater Controller AO4
247019 | A001