6
| How to set up the function
Step by step:
1.
Select Configuration from the navigation icons
2. Select I/O allocation settings
3. Select Analog inputs
4. Allocate Intake air temperature to AI4
5. Allocate Preheater temperature to UI1 on Controller
6. Go back to I/O allocation settings (use the navigation path Configuration > I/O allocation
settings)
7. Select Digital inputs
8. Allocate Feedback preheater to DI6
9. Select Feedback preheater
10.Adjust Contact function to Normally closed
11.Go back to I/O allocation settings (use the navigation path Configuration > I/O allocation
settings)
12.Select Analog outputs
13.Allocate Preheater to AO4
14.Go back to I/O allocation settings (use the navigation path Configuration > I/O allocation
settings)