IOM SPLIT AHU KIT 0 10V LNS20200113
8 I Installation and Operating Manual
6. FUNCTION AND SETTING
T2A/250VAC
ALARM DEFROST
CN1
CN2
LNS
HEAT
COOL
DEF.
POWER
POWER SUPPLY
&
COMMUNICATION
208
240VAC
FUSE:T2A 250VAC
/
ALARM
OUTPUT
max.
5A
250VAC;
5A
30VDC
DEFORST
OUTPUT
max.
5A
250VAC;
5A
30VDC
0-10VDC
INPUT
T2 Evaporator
Coil Temp
Sensor
HEATING
MODE
INPUT
COOLING
MODE
INPUT
COOLHEAT
ENC1
10V 0
T E MP 1
Recommended Cable
Cabling Typ of cable
Power supply & communication L, N, S
(between Outdoor Unit and SPLIT-AHU Kit 0-10V LNS)
3 x 1,5 mm²
LIYY
Communication Line
(between Air Handling Unit and SPLIT-AHU Kit 0-10V LNS)
10 x 0,25 mm²
LIYY
NOTE
» Cable selection in accordance with the local regulations.
» No low-voltage conductors and high-voltage conductors together in one
cable.