IOM SPLIT AHU KIT 0 10V LNS20200113

4 I Installation and Operating Manual
3. INTRODUCTION
The SPLIT-AHU Kit 0-10V LNS control module enables to control Single- or
Multisplit outdoor units with L, N, S communication. It allows to control
outdoor unit capacity as well as operation mode (heating or cooling) of an air
handling unit or a DX coil.
The control module enables to control inverter outdoor unit capacity between
0 - 10 % ~ 100 % by external input 0 ~ 10 VDC signal.
Dry contact signal is used to control outdoor unit to work in cooling or
heating mode.
SPLIT-AHU Kit 0-10V LNS have a temperature sensor and provide evaporator
froze protection.
The installation and operation of outdoor unit as well as controller must
be done according to the manuals (i.e. Users manual, Installation manual,
Technical Specication, Service manual).
4. SPECIFICATION AND PACKING LIST
Model SPLIT-AHU Kit 0-10V LNS
Casing Plastic
Dimension (h x w x d) 61 x 100 x 191 mm
Weight approx 0.4 kg
Operation Temperature Range -25 °C... +45 °C
Operation Humidity Range 40 - 90 %
Power Supply 230 VAC, 1 Phase, 50/60 Hz
Voltage Range 208 - 240 V
Fuse 15 A, 250 V
Resistance class IP54
Packing list
Box body 1 piece
Box cover 1 piece
Anti-water seal between box
body and box cover
1 piece
Temp sensor 1 piece
Gland 3 pieces
Manual 1 piece