TRVS15 25 Johnson Controls

PB_VG3000_03 2020
6
Operation
These valves are used for hot or cold water and for water
glycol mixtures up to 50%.
Note: These valves are intended to control equipment
under normal operating conditions.
Where failure or malfunction of the valves could
lead to an abnormal operating condition that
could cause personal injury or damage to the
equipment or other property, other devices (limit or
safety controls) or systems (alarm or supervisory
systems) intended to warn of or protect against
failure or malfunction of the valves must be
incorporated into and maintained as part of the
control system.
Mounting Instructions
General Guidelines
In addition to general installation instructions, please
observe the following points:
Ensure that valve body and piping are free of
impurities.
Pay attention to position of the valve relative to the ow
direction.
Note ow symbols on valve body.
Ensure that threaded connections of valve and piping
are tighten.
Ensure installation without tension and torque.
Do not use the valve as a step or xation point.
Only piping supports it.
Protect valve from dust or dirt on construction sites.
Provide strainer or lter upstream of valve.
Use compensators to balance thermal expansion of
piping.
Ensure that stem thread and shaft are kept free of
paint.