Technical Specications VG3000
Threaded Female Connection
Models VG3200xx
VG3240xx
VG3201xx
VG3241xx
VG3300xx
VG3340xx
Body Type 2-way
PDTC (NO)
2-way
PDTC (NO)
3-way
mixing
Body Rating PN16 Nominal, maximum rated pressure
Inherent Flow Characteristic Linear
Service Water, glycol solutions (max 50%) for HVAC applications.
Fluid Group 1 according Regulation (EC) No 1272/2008
(proper water treatment is recommended, refer to VDI 2035)
Body Size DN15 - DN20 - DN25
Max Pressure drop ∆p
DN15 70 kPa 80 kPa 70 kPa
DN20 50 kPa 60 kPa 50 kPa
DN25 40 kPa 50 kPa 40 kPa
Kv
s
and max. close-off pressure See “Ordering Code and Dimensions” on page 3
Body Connection Gas (ISO 228/1) and NPT
Nominal Stroke 4.0 mm
Connection to Actuator M30 x 1.5
Materials
Body EN12165 CW617 Brass CuZn40Pb2
Trim Stem: AISI 303 stainless steel (X10CrNiS1809)
Spring: AISI 302 stainless steel (X10CrNi1809)
Plug: EPDM
Leakage Max 0,01% of K
VS
, Class IV for ANSI FCI 70-2 and EN60534-4 modif. 1
Fluid Temperature Limits 2...110 °C
Ambient Temperature Limits 2...50 °C
Max weight packaging excluded 2-way NO 2-way NO 3-way mixing
DN15 279 g 318 g 273 g
DN20 383 g 428 g 383 g
DN25 509 g 539 g 509 g
Compliance Johnson Controls declares that these products are in compliance with the essential
requirements and other relevant provisions of the PED (Pressure Equipment Directive)
2014/68/EU (Paragraph 4.3).
CE marking is not applicable.
ROHS (2011/65/EU) when connected with an actuator.