Modbus for residential D24810 User manual(A007)

7.14Registersforalarms
NameRegister
address
RorR/W
NVMAccess
(Reg./Coil)
Description/remarks
REG_ALARMS_ALL
801R
Reg+CoilCoilAddress12801:Filteralarm
CoilAddress12802:Fanalarm
CoilAddress12803:Notused
CoilAddress12804:Rotoralarm
CoilAddress12805:Frostalarm
CoilAddress12806:PCU-PBalarm
CoilAddress12807:T emperaturesensor
alarm
CoilAddress12808:Emergency
Thermostatalarm
CoilAddress12809:Damperalarm
CoilAddress12810:LowSSalarm
CoilAddress12811:Defrostalarm
CoilAddress12812:RHsensor
Coilvalue0:alarmnotactive
Coilvalue1:alarmactive
REG_ALARMS_RELAY_ACTIVE
802R
Reg+CoilCoiladdress12817:alarmrelayactive.
0:Relaynotactive.
1:Relayactive.
REG_ALARMS_ALL_DETAILED
803RReg
Allalarmags,includingtemperature
sensorstatusags.
Bit0:Filteralarm
Bit1:Fanalarm
Bit2:Rotoralarm
Bit3:Frostalarm
Bit4:PCU-PBalarm
Bit5:Emergencythermostatalarm
Bit6:Damperalarm
Bit7:LowSSalarm
Bit8:Defrostalarm
Bit9:RHsensoralarm
Bit10:Supplyairsensoralarm
Bit11:Extractairsensoralarm
Bit12:Exhaustair/Preheatersensoralarm
Bit13:Overtemperature/Frostprotection
sensoralarm
Bit14:Outdoorairsensoralarm
ModbusforResidentialunitsUserManual
D24810
15
SystemairSverigeAB